Technical specifications

Flow rate max. (100% water)
Service
Accuracy up to 15 PSID = 100 kPa
Minimum ΔP for start-up
Maximum ΔP
Maximum working pressure
Close off pressure
Temperature
Connection
Leakage
Compliance
Flow rate max. (100% water)
Service
Accuracy up to 15 PSID = 100 kPa
Minimum ΔP for start-up
Maximum ΔP
Maximum working pressure
Close off pressure
Temperature
Connection
Leakage
Compliance
Table 1: VP140 Hxx 1/2" (DN15)
VP140HAA
0.66 GPM, 150 l/h
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
4.3 psi
30 kPa
Johnson Controls declares that these products are in compliance with
the essential requirements and other relevant provisions of the PED
(Pressure Equipment Directive) 2014/68/UE (Paragraph 4, comma 3).
CE Marking is not applicable.
ROHS (95/2002/CE)
Table 2: VP140 Jxx 3/4" (DN20)
VP140JAJ
4.4 GPM,1,000 l/h
Water or water-glycol mixture (up to 50% glycol), quality to VDI 2035
3.6 psi
25 kPa
Johnson Controls declares that these products are in compliance with
the essential requirements and other relevant provisions of the PED
(Pressure Equipment Directive) 2014/68/UE (Paragraph 4, comma 3).
CE Marking is not applicable.
ROHS (95/2002/CE)
17
VP140HDA
1.98 GPM, 450 l/h
± 5%
5.1 psi
35 kPa
87 psi
600 kPa
362 psi
2500 kPa
100 psi
689 kPa
14 to 248 °F
-10 to 120 °C
½" FNPT
ANSI Class IV IEC 60534-4
VP140JDB
8.1 GPM, 1,850 l/h
± 5%
87 psi
600 kPa
362 psi
2500 kPa
100 psi
689 kPa
14 to 248 °F
-10 to 120 °C
¾" FNPT
ANSI Class IV IEC 60534-4