MOD-BA module is DIN-rail mountable active redundancy module from Leuze electronic.
With the help of the redundancy module, two power supply units of the same type on the
output side are decoupled 100% from each other.
4
3
14
14
24
24
13
13
23
23
MOD-BA-I2/20-O2/
40A-24V
Art. No. 50132595
INPUT
INPUT
7
1
2
OK
OK
23
5
13
8
INPUT
INPUT
9
+24V
+24V
1
1
2
2
GND
GND
0V
0V
2
1
12
90
90
90
2 4
1 3
70
1
MOD-BA Module
MOD-EAC Module
2
15
Power
Supply 1
1
(max. 20A)
-
Power
Supply 2
(max. 20A)
Jumper
MOD-BA Module
1
MOD-EAC Module
2
16
Power
Supply 1
(max. 40A)
1
-
Jumper
Power
Supply 2
(max. 40A)
(1) General
The device may be installed only by trained and qualified personnel. MOD-BA module is
maintenance-free. Repairs can only be done by the manufacturer.
Balancing is achieved when input current is > 2 x 0,5 A and input voltage difference is
between 0 ... 300 mV 0% / -15% (2 x 10 A) or 0 ... 200 mV 0% / -15% (2 x 20 A).
Intelligent technology increases system efficiency in comparison to traditional technology
with diode. Current balancing technology makes possible to increase lifetime of power
supplies. If overheated balancing is disabled but unit continues to operate.
For high redundancy we recommend three-phase power supplies.
Only for use in pollution degree 2 environments.
Operating instructions
Redundancy Module
MOD-BA-I2/20-O2/40A-24V
3
6
7
24
5
14
8
9
GND
GND
0V
0V
2
13
≥
45
45
≥
0
mm
45
≥
3
14
Connector:
GND
LOAD
Contact for bridge:
(max. 20A, Ta = 60°C)
OUT
24
2
Control
OUT
-
23
24
13
14
Protected
Protected
LOAD
LOAD
OUT
Control
23
OUT
Take care about the temperature
resistance of your input and
output cable.
20A, Ta=60°C
10 mm² / AWG 8 16 mm² / AWG 6
≥
≥
80°C
75°C
GND
LOAD
(max. 40A, Ta = 60°C)
In case of 40A supply
circuit the wiring of each
power supply should be
2
carried out with two cable
-
-
- -
to the belonging MOD-BA
module.
Protected
Protected
LOAD
LOAD
(2) Technical specification, Art. No. 50132595
Nominal voltage
Input voltage range
Input current, I
Max. input current
Balancing (*)
Efficiency, typ.
Internal fuse for each channel
Protection against reverse polarity
Voltage drop, (Input to Output)
Output current max.
Derating
Power losses at full load:
Output 20 A: input from two 20 A supply
Output 40 A: input from one 40 A supply
Power losses at no load
Input transient protection
Output transient protection
Overload and overheating protection
Relative humidity
Ambient temperature
Storage temperature
10
Protection class, case, EN 60529
Dimensions W x H x D; Weight
(*) Input voltage difference must be < 300 mV 0% / -15%
(3) Features
[1] Input: +18 ... +30 VDC
Spring-loaded terminal
max. solid
max. stranded
Wire insulation temperature rating 75°C.
screwdriver blade: 0,6 mm x 2,8 mm
[2] GND, only for internal system electronics
Spring-loaded terminal
11
max. solid
max. stranded
Wire insulation temperature rating 75°C.
screwdriver blade: 0,6 mm x 2,8 mm
[3] Output
Spring-loaded terminal
max. solid
50mm
(1,97 in.)
max. stranded
Wire insulation temperature rating 75°C.
screwdriver blade: 0,6 mm x 2,8 mm
0
≥
[4] Alarm contact: 30 VAC/DC 100mA
mm
13/14 - Redundancy OK
23/24 - Balance OK
Spring-loaded terminal
50mm
(1,97 in.)
max. solid
max. stranded
Wire insulation temperature rating 75°C.
screwdriver blade: 0,6 mm x 2,8 mm
[5] Alarm contact jumper
[6] Status LED
Example of LED and Relay operation:
LED 1
LED 2
green
green
14
GND
GND
green
green
blinking
INPUT 2
green
red
INPUT 1
GND
red
red
13
GND
blinking
blinking
no color no color open
[7] Output jumper max. 40 A (total current)
[8] Module anchorage for bridging
[9] GND jumper max. 20 A (total current)
(4) Location [13]
MOD-BA module is cooled by natural convection. It is important to maintain clearance
to other components as much as possible to ensure best performance and long term
stability. Top and bottom clearances should be 50 mm at minimum. The ambient
temperature should be measured on the underside of the unit. There will be an increase
of 25°C at the top. If natural convection is restricted, forced cooling should be used.
Mounting should comply with EN 60950-1 point 4.7 and 4.6.1. Protection class of the
case IP20 (EN 60529).
(5) Mounting [12]
The rail should be fixed solidly so that it cannot twist when mounting or removing the
unit. Mounting instructions [10], Removing instructions [11].
IND.CONT.EQ.
61RM
(6) Principle diagram [14]
(7) Example of Application [15] and [16]
(8) Accessories
- Jumper set [5], [7], [8], [9]: MOD-ZBR-V1 (part. no. 50132611)
(9) Standards
EMC
Emissions
We reserve the right to change this specification.
om.
Relay
Relay
Remark
13/14
23/24
closed
closed
Input voltages are > 20,4 VDC ± 2 %, < 32 VDC ± 2 % and
balancing
closed
open
Difference between input voltages is > 300 mV (2 x 10 A) or
> 200 mV (2 x 20 A) - (channel 2 has smaller value)
open
open
Input voltage < 20,4 VDC ± 2 %, > 32 VDC ± 2 % -
(channel 2)
open
open
Overheating or overcurrent
open
Input- and output voltages are < 8 VDC / short circuit in
output
EN 61204-3 (2000) EMI: class B, EMS: industrial environment
EN 61000-4-2 (1995) ESD
EN 61000-4-3 (2002) RF-Field:
EN 61000-4-4 (1995) Burst
EN 61000-4-5 (1996) Surge
EN 61000-4-6 (1996) Cond. RF:
EN 61000-6-2
EN 61000-6-3
EN 55022 B (1998), RF-emissions
V1.0
+24 VDC
+18 ... +30 VDC
2 x 20 A
2 x 26 A (-25°C ... +40°C)
Input current > 1 A
> 99,5 % / 2 x 20 A
30 A
Yes
50 ... 350 mVDC
40 A continuous
+60°C ... +70°C (2,5% / K)
≤ 1,5 ... 4,5 W with balancing
≤ 3,3 W
0,36 W
yes
yes
yes
5 ... 95% , no condensing
-25°C ... +60°C
-40°C ... +85°C
IP20
70 x 90 x 80 mm; 0,15 kg
16 mm² / 6 AWG
10 mm² / 8 AWG
4 mm² / 12 AWG
4 mm² / 12 AWG
16 mm² / 6 AWG
10 mm² / 8 AWG
2,5 mm² / 13 AWG
2,5 mm² / 13 AWG
contact ± 6 kV, air ± 8 kV
10 V/m
± 2 kV, 5/50 ns
DC Input ± 500 V
DC Output ± 500 V
10 V