Fujitsu Airstage ABYA12GATH Manual De Instalación página 14

Ocultar thumbs Ver también para Airstage ABYA12GATH:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 50
Function details
Function
Function
Setting number
number
00
Default
Filter indicator
11
01
Longer
interval
02
Shorter
00
Enable
01
Disable
Filter indicator
Display
13
action
only on
02
central
remote
controller
00
Default
Horizontal swing
24
01
Left half
airfl ow direction
02
Right half
00
Default
Cool air
temperature
30
01
Adjust (1)
trigger
02
Adjust (2)
00
Default
Heat air
01
Adjust (1)
temperature
31
02
Adjust (2)
trigger
03
Adjust (3)
00
Enable
Auto restart
40
01
Disable
00
Super low
Cool Air
43
Follow the
Prevention
setting on
01
the remote
controller
00
Start/Stop
Emergency
External control
46
01
stop
Forced
02
stop
00
All
Display only
Error report
47
on central
target
01
remote
controller
Follow the
setting on
00
Fan setting
the remote
when cooling
49
controller
thermostat OFF
01
Stop
En-13
9367701100-01_IM.indb Sec1:13
9367701100-01_IM.indb Sec1:13
Default
Details
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too early,
change to setting 01. If the notifi cation is
too late, change to setting 02.
Enable or disable the fi lter indicator.
Setting 02 is for use with a central remote
controller.
Adjust the horizontal swing airfl ow
direction.
(For horizontal swing equipped models)
Adjust the cool air trigger temperature. To
lower the trigger temperature, use setting
01. To raise the trigger temperature, use
setting 02.
Adjust the heat air trigger temperature.
To lower the trigger temperature by 6
degrees C, use setting 01. To lower
the trigger temperature by 4 degrees
C, use setting 02. To raise the trigger
temperature, use setting 03.
Enable or disable automatic system restart
after a power outage.
* Auto restart is an emergency function such
as for power failure etc. Do not start and
stop the indoor unit by this function in
normal operation.
Be sure to operate by the control unit,
converter or external input device.
Restrain the cold airfl ow with making
the airfl ow lower when starting heating
operation. To correspond to the ventilation,
set to 01.
Allow an external controller to start or stop
the system, or to perform an emergency
stop.
* If an emergency stop is performed from
an external controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor unit stops by
the input to the external input terminals,
and Start/Stop by a remote controller is
restricted.
Change the target for reporting errors.
Errors can either be reported in all
locations, or only on the central remote
controller.
When set to 01, the fan stops when the
thermostat is OFF in cooling operation.
Connection of the wired remote controller
(2-wire type or 3-wire type) and switching
its thermistor are necessary.
7.4.1. Button name and function
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
MANUAL AUTO button
7.4.2. Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check the
function settings. It is necessary to disconnect the power in order to return to normal op-
eration mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indoor unit address
OPERATION indica-
ON
tor lamp (Green)
TIMER indicator lamp (Orange)
Address: tens place (0.5s ON/0.5s OFF)
FILTER indicator lamp (Red)
Address: ones place (0.5s ON/0.5s OFF)
• Indoor unit address example
(Example) ADDRESS : 24
OPERATION
ON
indicator lamp
(Green)
OFF
TIMER
ON
0.5s 0.5s 0.5s 0.5s
indicator lamp
(Orange)
OFF
ON
FILTER
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
indicator
OFF
lamp (Red)
• Refrigerant address example
(Example) ADDRESS : 30
OPERATION
ON
indicator lamp
1.0s
1.0s
(Green)
OFF
TIMER
ON
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
indicator lamp
OFF
(Orange)
ON
FILTER
indicator lamp
OFF
(Red)
• Setting details
Function number
Item
01
Indoor unit address
02
Refrigeration address
For use with a remote controller, set all rotary switches to 0, and refer to "7.1. Setting the
address" for details.
All switches are set to 0 at the factory.
Indication pattern
Refrigerant address
Flash (1.0s ON/1.0s OFF)
1 cycle 12 sec
ON
10 sec
8 sec
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
1.0s
9 sec
OFF
Setting number
00 to 63
00 to 99
2012-7-12 14:01:39
2012-7-12 14:01:39

Publicidad

Tabla de contenido
loading

Tabla de contenido