8.2 REFERENCES OF CONNECTING TERMINALS
Terminals ref.
L1 – L2 – L3 -
U – V – W -
U1 – V1 – W1
U – V – W -
U1 – V1 – W1
U – V – W -
U1 – V1 – W1
3
TRP1
1 – 2 – 3
TRP2
1 – 4 – 5 – 6
P.S. MIN.
7 – 8
P.S. 1.
9 – 10
P.S. 2.
11 – 12
P.S. 3.
13 – 14
R. C.
15 – 16
INP. AN.1
17 – 18 – 5
OUT. AN.1
18 – 19
ENGLISH
Connections of the supply line to the main isolating switch QS1.
ATTENTION! CONNECT THE EARTH LEAD CORRECTLY.
Connections of the electropump P1.
Strictly respect the correspondence provided.
ATTENTION! CONNECT THE EARTH LEAD CORRECTLY.
Connections of the electropump P2.
Strictly respect the correspondence provided.
ATTENTION! CONNECT THE EARTH LEAD CORRECTLY.
Connections of the electropump P3.
Strictly respect the correspondence provided.
ATTENTION! CONNECT THE EARTH LEAD CORRECTLY.
Connection terminals of the pressure transducer ONE.
Terminals ref.: 1=
ATTENTION, CONNECT THE SCREEN TO TERMINAL 1.
Connection terminals of the pressure transducer TWO.
Terminals ref.: 1=
ATTENTION, CONNECT THE SCREEN TO TERMINAL 1.
Connection terminals of the minimum pressure switch.
(connect only contacts without voltage)
Connection terminals of the control pressure switch of
electropump ONE.
(connect only contacts without voltage)
NOT CONNECTED.
Connection terminals of the control pressure switch of
electropump TWO.
(connect only contacts without voltage)
Connection terminals of the control pressure switch of
electropump THREE.
(connect only contacts without voltage)
Connection terminals of a remote control configurable to
parameter 300.
Terminals ref: 15= inp., 16=power.
(connect only contacts without voltage)
Connection terminals of the potentiometer PSET EXT to be
set in parameter 102.
Terminals ref.: 17=INP, 18=GND, 5= power.
(connect potentiometers 10 k-ohm 1 W)
Connection terminals of an external instrument configurable
to parameter 303.
Terminals ref. : 18=GND, 19= OUT.
(connect instruments with max. absorption 5 mA, 10 V)
FUNCTION
, 2= power 3= inp.
, 4= GND, 5=power, 6=inp.2.
77