Wiring the GRAFIK Eye
Line Voltage Wiring Details
• Use properly certified cable for all line
voltage/mains cables.
• Proper short-circuit and overload
protection must be provided at the
distribution panel.
• Install in accordance with all local and
national electrical codes.
• IEC PELV terminals may be temporarily
unplugged for ease of IR, occupancy
sensor, and control wiring.
• Notice: Risk of damage to unit . Do not
connect line voltage/mains cable to IEC
PELV terminals.
Step 1: Install wallbox. Mount a 89
mm deep 4-gang U.S. wallbox on a dry,
flat indoor surface that is accessible
and allows for system programming
and operation. Allow at least 110 mm
clearance above and below the faceplate
to ensure proper heat dissipation. Allow
25 mm for faceplate overhang on all
sides.
Note: 4-gang wallbox available from
Lutron; P/N 241400.
Faceplate overhangs
wallbox on all sides;
allow 25 mm
LUTRON
110 mm
LUTRON
®
QS with DALI Control Unit:
®
Step 2: Check control unit wiring.
• Earth/ground terminal connection must
be made as shown in line voltage wiring
diagrams.
• Follow all local and national electrical
codes when installing IEC PELV wiring
with line voltage/mains wiring.
WARNING! Shock hazard. May
result in serious injury or death.
Always turn off circuit breaker or
remove main fuse from power
line before doing any work.
Before connecting the loads to
the GRAFIK Eye
control unit, test the loads for
short-circuits.
Step 3: Connect line voltage and loads
to control unit.
• Strip 8 mm of insulation off the line
voltage/mains cables in the wallbox.
• Connect the line voltage/mains, ground,
and load wires to the appropriate
terminals on the back of the control unit.
L: Hot/Live
N: Neutral
: Ground
The recommended installation torque
is 0.6 N∙m for line voltage/mains
connections and 0.6 N∙m for the earth/
ground connection.
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye
QS with DALI
®
8 mm
QS with DALI Control Unit Quick Installation and Operation Guide 4
®
Notice: Risk of damage to unit. GRAFIK
Eye
QS with DALI control units must
®
be in stalled by a qual i fied electrician in
accordance with all applica ble reg u la-
tions and building codes. Im prop er wiring
can result in dam age to control units or
oth er equipment.
Note: To avoid over heat ing and pos-
si ble damage to equipment, do
not install control units to dim
re cep ta cles, mo tor-op erated ap pli-
ances, or flu o res cent lighting not
equipped with DALI electron ic
dim ming ballasts, or other DALI
devices approved for your location.
Control units are de signed for res-
i den tial and commercial use, for
indoor use only.