Descargar Imprimir esta página

Eaton CROUSE-HINDS Serie Guia De Inicio Rapido página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

WIRE GUARD INSTALLATION
Loosen but DO NOT completely remove wire guard screw. If already
loosened, move to next step.
Set wire guard in place by pushing it over the bottom rim of the
luminaire which is on the lowest casting until it sits in place above
that rim. Ensure that the wire guard is in place around the complete
bottom and is not partially in place above the rim.
Tighten the screw attached to wire guard until guard is securely
attached to bottom casting. The screw will be tight enough when the
wire guard can no longer easily rotate on the luminaire.
NOTE: The sheet metal tabs which the screw goes through do not
need to be touching for the guard to be securely fastened; the wire
guard will be secure without those two tabs touching one another.
FIELD ASSEMBLED LUMINAIRES
Champ
VMVL and PVML Series Luminaires
®
MOUNTING MODULE SERIES
PENDANT
ANGLED
CEILING
WALL
APM2
BPM2
CM2
TWM2
APM3
BPM3
CM3
TWM3
HPM2
VMVL
VMV*L
PVML
PVM*L
MAINTENANCE
1.
Perform visual, electrical and mechanical inspections on
a regular basis. The environment and frequency of use
should determine this. However, it is recommended that
checks be made at least once a year. We recommend an
Electrical Preventive Maintenance Program as described in the
National Fire Protection Association Bulletin NFPA No. 70B:
Recommended Practice For Electrical Equipment Maintenance
(www.nfpa.org).
2.
The lens should be cleaned periodically to ensure continued
lighting performance. To clean, wipe the lens with a clean,
damp cloth. If this is not sufficient, use a mild soap or a liquid
cleaner such as Collinite NCF or Duco #7. Do not use an
abrasive, strong alkaline or acid cleaner. Damage may result.
3.
Visually check for undue heating evidenced by discoloration
of wires or other components, damaged parts or leakage
evidenced by water or corrosion in the interior. Replace all
worn, damaged or malfunctioning components, and clean
gasket seals before putting the luminaire back into service.
4.
Electrically check to make sure that all connections are clean
and tight.
5.
Mechanically check that all parts are properly assembled.
IF 1882 • 07/19
Copyright © 2019, Eaton's Crouse-Hinds Division
CHAMP LED SAFETY CABLE (NEC/CEC ONLY)
1.
Pass cable through the Kwik-Loc adjustment
hole in the direction of the arrows (see
Figure 3).
2.
Locate attachment point in between two (2) of
the housing fins, as shown in Figure 4.
3.
Route secondary retention cable through
attachment point on the fixture housing and back through the
Kwik-Loc second adjustment pin hole in the direction of the
arrows.
4.
Connect cable to a
permanent structure,
or anchor (customer
supplied).
5.
Remove any slack to
ensure the cable is taut
and confirm engagement
of the lock.
FIGURE 4
MOUNTING MODULE NOTES:
STANCHION
- 2: indicates 3/4" NPT thread
- 3: indicates 1" NPT thread
JM5
PM5
- 4: indicates 1-1/2" thread
- Pendant, angled, ceiling and stanchion mounts
have one (1) conduit entry; ceiling and wall
mounts have five (5) conduit entries
REPLACEMENT PARTS
Eaton's Crouse-Hinds series VMVL and PVML Series Champ
Luminaires are designed to provide years of reliable lighting
performance. However, should the need for replacement parts arise,
they are available through your authorized Eaton's Crouse-Hinds
distributor. Assistance may also be obtained through your local Eaton's
Crouse-Hinds representative.
Eaton's Crouse-Hinds Sales Service Department, 1201 Wolf Street,
Syracuse, New York 13208, Phone (866) 764-5454.
WARNING
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance. Luminaire must be supplied by a wiring system with
an equipment grounding conductor.
FIGURE 3
To avoid burning hands:
Make sure luminaire is cool when performing maintenance.
INSTALLATION CHECKLIST
1._______ Verify sufficient HTL lubricant is on conduit plugs
(recommend approximately 1/8" bead around the first
thread of plug) and that all unused conduit entries on
the cover module are closed with lubricated plugs.
2._______ Verify conduit plugs are installed to at least five (5)
full threads into the cover module conduit entries.
3._______ Verify installed conduit plugs are torqued to 42-52
ft.-lbs. for 3/4" plugs and 58-68 ft.-lbs. for 1" plug.
4._______ Verify supply wires are connected to luminaire wire
leads (or terminal block) per wiring diagrams.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be
reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Eaton's Crouse-Hinds Division's "Terms and
Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine the suitability of the product
for his intended use and assumes all risk and liability whatsoever in connection therewith.
Page 3
5._______ Verify all electrical connections are tightened.
6._______ Verify all wires are safely and neatly inside driver
housing and not on top of wire terminal. Close driver
housing onto cover module.
7._______ Verify captive closing screw is tightened to 30 in.-lbs.
(3.4 N-m) and two (2) bosses on driver housing are in
contact with cover module.
Eaton's Crouse-Hinds Division
1201 Wolf Street, Syracuse, New York 13208
Copyright © 2019
IF 1882
Revision 1
New 07/19

Publicidad

loading

Este manual también es adecuado para:

Crouse-hinds champ vmvlCrouse-hinds champ pvml