Connecting Digital Inputs: Power Setpoint - Ingeteam INGECON SUN ComBox Manual De Instalacion Y Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 61

Connecting digital inputs: power setpoint

7. Connecting digital inputs: power setpoint
On the INGECON SUN ComBox base plate 4 digital inputs are provided that allow the power supplied by the
inverters to be monitored.
These inputs are set to be monitored every 30 seconds, and in the event they present changes INGECON SUN
ComBox sends power limitation data to the inverters via a broadcast.
These inputs accept voltage inputs within the range of 0 ~ 15 V, and the corresponding setpoint value is
determined by the following table:
The power setpoint function is configured in the INGECON SUN Manager software.
See section "11.2. Configuration and monitoring" in this manual in order to configure the digital
inputs.
AAX2015IQM01_ - Installation and usage manual
+15
GND
D4
D3
D2
J12
D1
Input
All at 0
Two or more at 1
D1
D2
D3
D4
Setpoint
100%
100%
0%
30%
60%
100%
Ingeteam
DE
EN
ES
FR
IT
PT
45