SVGm IP54
If the display has entered energy saving mode, it is automatically disabled. The alarm screen disap-
pears when the display is touched.
Description
The SVGm IP54 current is too high.
Corrective
This alarm may be associated with transients and noise in the power supply voltage. Check the quality
action
of the power supply voltage. If it continues, contact the TAS.
Description
The mains voltage is too high.
This alarm may be associated with transients and noise in the power supply voltage, or with incorrect
Corrective
mains voltage values. Check the configuration. Check the quality of the power supply voltage. If it
action
continues, contact the TAS.
Description
The temperature of the power module is very high.
Corrective
Check that the fans are working. Clean or replace them if necessary. If it continues, contact the TAS.
action
Description
The temperature of the inductors is very high.
Corrective
Check that the fans are working. Clean or replace the fans if necessary. If it continues, contact the TAS.
action
Description
The start-up conditions have not been met 10 times during the past 5 minutes.
Corrective
Check the configuration and the ambient temperature. Check the quality of the power supply voltage.
action
If it persists, contact the TAS.
Description
Failure in internal communications.
Corrective
Restart. Contact the TAS.
action
Description
The self-diagnostic system has detected a fault.
Corrective
Contact the TAS.
action
Description
Internal error.
Instruction Manual
Figure 41: Permanent alarms.
Table 12: Alarm messages.
Alarm messages
Overcurrent L1/L2/L3
Mains overvoltage L1/L2/L3
High temp IGBT
High temp Inductor
Initial Conditions
Internal communications
Hardware failure
Exxx or Cxxx