Protocol; Example Of Modbus Query; Modbus Map - Circutor SVGm IP54 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SVGm IP54

8.2.- PROTOCOL

In the Modbus protocol, the SVGm IP54 uses the RTU (Remote Terminal Unit) mode.
The Modbus functions implemented in the device are as follows:
Functions 03 and 04: Reading of n Words (2 bytes).

8.2.1.- EXAMPLE OF MODBUS QUERY

Query: Value of the Load current of L1
Address: 0A, Peripheral number: 10 in decimal.
Function: 03, Read function.
Initial Register: 92, register from which to start reading.
No. of registers: 0002, number of registers to be read.
CRC: xxxx, CRC character.
Response:
Address
0 A
Address: 0A, Responding peripheral number: 10 in decimal.
Function: 03, Read function.
No. of bytes: 04, No. of bytes received.
Register:
000000FA,
CRC: xxxx, CRC character.

8.2.2.- MODBUS MAP

All Modbus map variables are in hexadecimal format.
For these variables, Functions 03 and 04 are implemented.
8.2.2.1.- Load Measurements
Parameter
Current with Load
Active power with Load
Reactive power with Load
Apparent power with Load
cos ɸ with Load
Instruction Manual
Address
Function
register
0A
03
Function
No. of Bytes
03
04
value of load current L1, with 1 decimal: 0xFA = 25.0 A
Table 14: Modbus memory map: Measurements with Load.
L1
L2
L3
93 - 92
95 - 94
97 - 96
AD - AE
AF - B0
B1 - B2
B3 - B4
B5 - B6
B7 - B8
B9 - BA
BB - BC
BD - BE
D1
D2
D3
Initial
No. of
CRC
registers
92
0002
xxxx
Register no. 1
Register no. 2
0000
00FA
LN
99 - 98
[Hi] + [Low] A with 1 decimal
-
kW with 2 decimal places and sign.
-
kVar with 2 decimal places and sign.
-
kVA with 2 decimal places and sign.
-
CRC
xxxx
Units
With 3 decimal
129

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido