PR electronics 6333 Manual Del Producto página 20

Transmisor de 2 hilos programable
Ocultar thumbs Ver también para 6333:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

LERBAKKEN 10, 8410 RØNDE DENMARK.
Hazardous (Classified ) Location
Class I, Division 2, Group A,B,C,D T4..T6
Class I, Zone 2, IIC T4..T6
Installation notes.
The Transmitter must be installed in a suitable enclosure to meet installation codes stipulated in The
National Electrical Code (ANSI-NFPA 70).
To assure a Non-Incendive system the transmitter and associated apparatus must be wired in
accordance with the associated apparatus manufacturers field wiring instructions and the circuit
diagram shown above.
.
Revision date:
2014-09-17
20
FM Installation drawing 6333QF01
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
43
13
12
42
11
41
CH1
23
53
22
52
21
51
CH2
6333A1A: one channel
6333A1B: two channel
Version Revision
V1R0
WWW.PRELECTRONICS.COM
Non Hazardous Location
Associated
apparatus
+
-
Associated
apparatus
+
-
6333V104-ES
Terminal:
11,12,13 and
21,22,23
Vmax: 35 VDC
Li: 10μH
Ci: 6.2nF
Page:
2/2

Publicidad

Tabla de contenido
loading

Tabla de contenido