3.2.3 Pressure Setup
Menus
Setup Menu
SET PRESSURE
SET PRESSURE 2
HIGH LIMIT ALARM
LOW LIMIT ALARM
PRESSURE
SETUP
START LEAD PRESSURE
START LAG PRESSURE
STOP LAG PRESSURE
3.2.4 Control Setup
Menus
Setup Menu
P
I
D
CYCLE TIME
ALTERNATION
FRICTION
RUN DELAY
STOP DELAY
CONTROL
JOCKEY STOP DELAY TIME
SET UP
OPERATION TYPE
LOW SUCTION TMR
LOW SUCTION RST
LOW SUCT RST TMR
LOW PRESS STOP TIME
INITIALIZE
SJE-Rhombus VFDC-4100 Controller User Manual
Contents
Target pressure for the pump system discharge
To change the set pressure to this alternate
value, a dry contact must close between G-COM
and 018 on the CN8 terminals.
If the discharge pressure exceeds this value, the
controller will shutdown the pumps after a delay.
If the discharge pressure drops below this value,
the contoller will shutdown the pumps after a
delay.
If the set pressure is 60 PSI and start lead
pressure at -3 PSI, the lead pump will start
when the operating pressure drops below 57 PSI.
If the set pressure is 60 PSI and start lag
pressure is -7 PSI the lag pump(s) will start when
if lead pump is operating full speed (100% and
the system pressure drops below 53 PSI.
If the set pressure is 60 PSI and the stop lag
pressure is 3 PSI the lag pump will stop if it is
operating at minimum speed (example 50%)
and the current pressure is over 63 PSI.
Contents
P Value Setup of PID (Proportional)
I Value Setup of PID (Integral)
D Value Setup of PID (Derivative)
Sampling time of PID Control
Shifts the lead to the next available pump in the
sequence.
PSI offset allowance for friction loss
Delay time for pumping output to start
Delay time for pumping output to stop
Delay time after the main pump starts
Sets the operation type. VFD = multiple VFD
control system (1 VFD for each pump.)
1VFD+ATL = Single VFD control system
(combination of 1 VFD and starters)
Delay time before stipping the pump due to low
suction pressure
Method used to reset the low suction shut
down valve
When low scution rest is set to auto, this is the
time the controller will wait before attempting
to reset.
Delay time before stopping the pump due to low
pressure fault.
All parameters are set to factory defaults
(except data setup)
Input Range
2 PSI ~ 650 PSI
2 PSI ~ 650 PSI
3 PSI ~ 719 PSI
1 PSI ~ 649 PSI
-65 PSI ~ 65 PSI
-65 PSI ~ 65 PSI
0 PSI ~ 65 PSI
Input Range
0 ~ 200
0 ~ 200
0 ~ 200
0 ~ 999 m.sec
0 ~ 999 HOURS (set to 0 for
lead. Change every cycle, set
to 999 for no alternation)
0 PSI ~ 900 PSI
0 ~ 999 SECONDS
0 ~ 999 SECONDS
0 ~ 999 SECONDS
VFD, 1VFD+ATL
10 ~ 999 SECONDS
AUTO, MANUAL
10 ~ 999 SECS (2.78 hrs)
10 ~ 999 SECONDS
YES, NO
11