Wieland SNO 4083KM Manual De Instrucciones página 14

Ocultar thumbs Ver también para SNO 4083KM:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 32
Terminals and connection data
Single-core or finely stranded
Finely stranded with wire-end ferrule according to
DIN 46228
AWG conductor size (only use Cu wires)
Maximum tightening torque
Stripping length
General data
Air gap and creepage paths between the circuits
Output circuits 1
Output circuits 2
Power circuit
Control circuits
Safety separation
– Rated voltage 300 V
– Overvoltage category IV (6kV)
Basic insulation
– Rated voltage 300 V
– Overvoltage category III (4kV)
Protection class according to EN 60529
case/terminals
Ambient operating temperature
Storage temperature
Weight
Standards
Certifications
11 Error codes and correction
Flashing code (SUPPLY-LED)
2
Crossover, can be rectified during operation
3
Process error, failure to observe the correct sequence for two-channel actuation, can be rectified during opera-
tion by repeating the actuation sequence correctly
4
Synchronous time error, synchronous time exceeded in the case of two-channel actuation, can be rectified
during operation by adhering to the synchronous time
5
Maximum reset actuating time exceeded, can be rectified during operation by repeating the reset with the
correct time
6
Configuration error, can be rectified by ensuring the correct terminal assignment for the required configuration,
the device has to be switched off and on again
7
Permissible input voltage limits undershot / overshot at S12 and S22, can be rectified by setting the correct
supply voltage, the device has to be switched off and on again
8
Device temperature too high, can be rectified by reducing the contact loads or the ambient temperature, the
device has to be switched off and on again
≥ 12
Internal monitoring event, please replace the device and contact after sales service
If an error is still indicated even after the cause has been rectified, inputs S12, S22, S14 and S34 must be kept open during
power-on (e.g. pull out the connector). The error should then be cleared and you can perform a restart with the required installa-
tion by means of a power-off and power-on operation.
Doc. # BA000773 – 07/2017 (Rev. I)
Screw terminals
1 x 0,2 mm² bis 2,5 mm²
2 x 0,2 mm² bis 1,0 mm²
1 x 0,25 mm² bis 2,5 mm²
2 x 0,25 mm² bis 1,0 mm²
26–14
0,5 bis 0,6 Nm (5-7 lbf-in)
EN 60664-1
13/14 and 23/24
33/34 and 41/42
A1/A2
S11, S12, S21, S22, S14 and S34
Output circuits 1
— Output circuits 2
Output circuits 1 and 2— Power circuit
Output circuits 1 and 2— Control circuits
Output circuits 1
Output circuits 2
Power circuit — Control circuits (only 115-230 V AC)
IP40 / IP20
–25 to +65 °C (UL508: -25 to +55°C)
–25 to +75 °C
0.2 kg
EN ISO 13849-1, EN 62061, EN 81-20, EN 81-50, EN 50156-1
TÜV, cULus
SNO 4083KM
Spring-loaded terminals (TWIN)
1 x 0,2 mm² bis 1,5 mm²
1 x 0,25 mm² bis 1,5 mm²
24–16
7 mm
EN 14

Publicidad

Tabla de contenido
loading

Tabla de contenido