ADJUSTMENT OF THE POWER AND
OPERATIONAL TIMES
The power and operating times may be adjusted by means of 3
trimmers located on the control unit:
POWER:
motor power.
WORK:
motor operating time (2 - 120 seconds).
PLEASE NOTE: it is recommended that operating times be
set with the slow down function disabled (DIP 5 OFF).
WARNING: the adjustment of times has to be made
when the gate is still
PAUSE:
pause time before automatic re-closure
(2 - 150 seconds).
CABLE GLAND ASSEMBLY
The casing can accept 4 cable glands in the special
easy-break housings.
The type of cable gland is indicated in the figure.
PLEASE NOTE:
• Remove the electronic circuit board before drill
the casing.
• Drill the container using a suitably sized cutter,
according to the dimensions of the cable gland.
• Fix the cable glands using the special nuts.
CONTROL UNIT INDICATORS (LEDS)
The highlighted boxes indicate the state of the LEDs when the
gate is resting.
LED
ON
START
START input closed
IN2
START P. input closed
STOP
STOP input closed
PHOTO PHOTO input closed
EDGE input closed (edge
not pressed)
EDGE
EDGE input closed
(edge pressed)
Edge NO pressed: 8K2
between EDGE input and
common (-)
FCA
Opening limit switch closed Opening limit switch open
FCC
Closing limit switch closed
mains
Control unit powered-up
Accessory power supply
overload
overload
9
OFF
START input open
START P. input open
STOP input open
PHOTO input open
Standard edge
EDGE input open (edge
pressed)
Resistive rubber edge
EDGE input open
(fault)
Closing limit switch open
Control unit NOT powered-up
Accessory power supply within
normal operational limits