- while the gate is closing, the gate will open
- while the gate is opening, the gate will close.
In case the safety strip is held pressed a further quick reversion, after 2 seconds, is performed. The
gate interrupts any movement and this alarm state is indicated by 1 minute Blinker flashing. The normal
gate operations can be restored by pressing any push button or radio commands.
The safety strip input (EDGE - COM) is a NORMALLY CLOSED contact.
In case there are more than one safety strip, all their contacts must be connected in series.
In case the safety strip is not installed, this contact must be short circuited with a wire
jump (from EDGE to COM) to permit the gate to operate and the Safety Strip test must be
disabled (DIP 13 OFF).
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if photocell fails or remain
engaded for more than 60 seconds, the K BUTTON and PEDESTRIAN commands will work only in
dead man mode.
The signal that this mode has been activated is given by the blinking of the programming led.
With the blinking of the programming led, the opening and closing operation are allowed only with
the command button pressed and held. The radio commands and that of automatic closing, will be
excluded, since their use in this mode, is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard commands that
were selected, such as step by step, automatic mode, radio commands and automatic closing start
functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the safety strips (or photocells)
the photocells (or safety strips) still work by interrupting the operation in progress.
During the dead-man operation, press and hold the K BUTTON or the PED BUTTON for the complete
operation, and until the switching off of the leds of the motors (DL3 - DL5 total opening M2 - M1 -
pedestrian DL5 - DL4 - DL6 total closing M2 - M1 - pedestrian DL6), or of the blinker, when installed.
The dead-man operation is only an emergency operation which must be activated for a
very short period and with the complete installation at sight so to have a secure and safe
control of the system. As soon as possible however, the failing safety devices must be
repaired and activated.
TESTING THE SAFETY STRIP equipment
The switch DIP13 ON enables to test the safety strip equipment. The test is performed every time the
gate completes a full opening. The test is available only if the safety strip device is equipped
with a dedicated power supply input. In fact, the safety strip equipment power supply input can
be connected to the A+TEST and A- outputs (DIP13 ON). Automatically, every time the gate completes
a full opening, just before closing, the control board switches OFF the A+TEST and A- power supply
output for a very short time. While the safety strip power supply is switched OFF, if everything is
working fine the safety strip contact (EDGE - COM) must open. In case the test fails, no other gate
manoeuvre will be allowed.
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH DIP13 MUST BE LEFT OPEN.
BLINKER
Connect the flashing light to the blinker output, use flashing lights ACG7059 and bulbs of 40W
maximum.
PRE-FLASHING function
The DIP 5 in the ON position enables the pre-flashing, the BLINKER starts flashing 3 seconds before
every movement of the gate. The DIP 5 in the OFF position disables any pre-flashing, the BLINKER
starts flashing and the motors will start at the same time.
BUZZER
The current supplied to the Buzzer will be 200 mA at 24 Vdc.
During the normal operation of the gate, opening and closing, the buzzer will buzz intermittently. Only
during the alarm situations (safety strip) the buzzing will almost be constant.
GATE OPEN INDICATOR (SIGNAL - COM)
Should you need to have an indication about the leaf position, the output SIGNAL - COM can be
TROUBLE SHOOTING
After having carried out all connections, by carefully following the layout and having positioned the gate in intermediate position, check the correct ignition of LEDS DL7, DL8.
In case of no ignition of the LEDS, always with gate in intermediate position, check the following and replace any faulty components.
DL7
switched off
Faulty photocells
DL8
switched off
Faulty safety edge (In case the edge is not connected, carry out jumper between COM and EDGE)
During functioning with personnel present, with DIP 1 at ON, check that during opening of M1 and M2 the green DL5 and DL3 LEDS switch on and that during closing of M1 and M2 the red DL6 and DL4 LEDS switch on.
If not, invert clamps V and W on the motor terminal board of the interested motor.
After having carried out the various connections and having supplied voltage, all the LEDS are
switched off.
The motor opens and closes, but it has no strength and moves slowly.
The gate opens but does not close after the time set.
The gate does not open or close by activating the various K and RADIO buttons.
By activating the K button the gate does not move.
The electric lock does not work.
FAULT
connected to a 24 Vdc bulb of 3W maximum. It is turned ON when the gate is open or partially open,
it is turned OFF only when the gate is completely closed.
WE RECOMMEND NOT TO OVERLOAD THE INDICATOR OUTPUT (SIGNAL - COM) OTHERWISE THE
GATE FUNCTIONING COULD BE COMPROMISED OR THE CONTROL BOARD COULD BE DAMAGED
RESTORATION OF OPERATIONS AFTER A BLACKOUT
If DIP 11 is turned OFF the blackout function is DISABLED.
If DIP 11 is turned ON the blackout function is ENABLED.
In case of a blackout occurs and the blackout function is enabled (DIP11 ON), when the main power returns,
automatically the operator will function according to the chart 1.
During blackout
If the gate is totally closed
If the gate is opening
If the gate is totally open (with DIP3 OFF)
If the gate is totally open (with DIP3 ON)
If the gate is closing
If the gate is in the safety edge alarm state The safety edge alarm will renewed
TECHNICAL SPECIFICATIONS
- Humidity
- Power supply voltage
- Frequency
- Maximum absorption
- Interruptions in electricity supply
- Maximum power of gate open indicator 24 Vdc
- Maximum load of blinker output
- Current available for photocells and accessories
- Current available on radio connector
TECHNICAL RADIO SPECIFICATIONS (Only CRX models)
- Reception frequency
- Impedance
- Sensitivity
- Excitation time
- De-excitation time
- Codes in store
- All the inputs must be used as clean contacts because the power supply is generated internally (safe
voltage) in the card and it is set in a way to guarantee the use of the double insulation and reinforced
in relation to parts with hazardous voltage.
- Any external circuits connected to the outputs of the control board, must be carried out to make sure
the double or reinforced insulation is used in relation to parts with hazardous voltage.
- All the inputs are run by a programmed integrated circuit which carries out a self-check at the
beginning of each operation.
Check the integrity of fuses F1 and F2. In case of interrupted fuse use only of adequate value
F2 = 5A F1 = T315mA.
Check trimmers TORQUE and LOW-SPEED adjustment.
Ensure to have set DIP 3 at ON. Button K BUTTON always inserted in automatic functioning mode
(DIP 6 OFF). Replace button or switch of the selector switch.
Failed edge self-test => check the connections between electronic board and edge feeder.
Attention: if not using a feeder for edges, DIP 10 must be at OFF position.
Faulty safety edge contact. Faulty photocells contact with DIP 4 OFF.
Fix or replace the relative contact.
Impulse K always inserted. Check and replace any buttons or micro-switches of the selector switch.
Ensure to have enabled DIP 8 at ON.
33
CHART 1
At the return of the main power supply
It will remain closed
It will continue opening
It will remain open, waiting for any command
It will remain open and then, when the time
of the Automatic Closing is expired, the
gate will close
It will continue closing
< 95% without condensation
230 o 120V~ ±10%
50/60 Hz
36 mA
100ms
3W (equivalent to 1 bulb of 3W or 5 LED with
serial resistance of 2,2 kΩ)
40W with resistive charge
500mA 24 Vdc
200mA 24 Vdc
433,92MHz
52 Ω
>2.24µV
300ms
300ms
N° 62 total
SOLUTION
G
B