Electrical installation

Connection data

6.3
Connection data
Mains
Terminal X301
Terminal data
E94AZxS0544
E94AZxS0954
PE connection data
E94AZxS0544
E94AZxS0954
Standard device
Cable X302
6.4

Mounting steps

Proceed as follows to connect the filter:
1. Connect the filter output cable (X302) to terminal X100 of the standard
device.
2. Connect the mains cable to terminal X301.
3. Attach the supply−side PE conductor to the PE conductor screw using a
ring or fork−type cable lug.
The PE connection must comply with EN 61800−5−1.
46
Labelling
Description
L1
Connection of the mains phases L1, L2, L3
L2
L3
+
Connection for the supply−side PE conductor with ring cable
lug M8
SSP94FF606
Max. conductor cross−section
2
[mm
]
50
95
Æ
[mm]
M8
Labelling
Description
1
Filter output conductor (lead with wire end ferrules, colour
BK)
2
3
PE
Output−side PE conductor (lead with wire end ferrule,
colour GN/YE)
SSP94FF607
Tightening torque
[AWG]
[Nm]
0
10
000
14
Starting torque
[Nm]
12
l
!
[lb−in]
88.5
Hexagon
socket 5
124.0
!
[lb−in]
106
SW 13
EDK94AZRS6 DE/EN/FR/ES/IT 7.0