5 - PROGRAMMABLE FUNCTIONS
5.5 - SELECTING THE TEMPERATURE
ADJUSTMENT METHOD
(ON/OFF DIFFERENTIAL or PROPORTIONAL)
This procedure allows the user to select the temperature
adjustment method:
Proportional
.
EN
Mode
Mode
Mode
34
Differential
(default setting) or
Set the temperature
adjustment method via
the
or
button.
OK
Press
OK
to save and
move on to the sub-
sequent setting or keep
the button pressed for at
least 4 sec to save the new
setting and exit the
programmingmenu.
OK
OK
5.6 - HYSTERESIS SETTING
The Hysteresis value for the thermal differential adjustment mode
ON/OFF (
)
must be set according to the system's thermal
inertia; a low value is recommended for systems with radiators
made of e.g. cast iron and a high value for systems with fan coils.
The value is adjustable from 0.2 °C to 1.2 °C and the default
setting is 0.5 °C.
Mode
OK
Mode
OK
Mode
OK
Set the hysteresis value
via the
or
button.
Press
OK
to save and
move on to the sub-
sequent setting or keep the
button pressed for at least 4
sec to save the new setting
and exit the programming
menu.