LERBAKKEN 10, 8410 RØNDE DENMARK.
For safe installation of 6335A or 6337A the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws, directives
and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
IECEx Certificate
Marking
Standards
T6: -40ºC to 60 ºC
T4: -40ºC to 85 ºC
Terminal:
41,42,43,44 /
51,52,53,54
Ex nA [ic]
Uo: 9.6 VDC
Io: 28 mA
Po: 67.2 mW
Lo: 35 mH
Co: 3.5 μF
Revision date:
2014-06-20
16
IECEx Installation drawing
IECEx KEM.10.0084X
Ex nA [ic] IIC T6..T4 Gc
Ex ic IIC T6..T4 Gc
Ex ic IIIC Dc
IEC60079-0: 2011, IEC60079-11:2011, IEC60079-15:2010
Hazardous Area Zone 2 or Zone 22
44
43
42
41
54
53
52
51
Version Revision
V4R0
WWW.PRELECTRONICS.COM
14
Terminal:
13
+
11,12,13,14
12
-
21,22,23,24
11
Ex nA
CH1
U ≤ 35 VDC
Ex ic
24
Ui : 35 VDC
23
+
Li : 10 μH
Ci : 1.0 nF
22
-
21
CH2
6335A
6337A
6335V111-ES
6335QI02