1. Ex marking
Supplementary documentation:
▶
This additional information for hazardous areas applies in conjunction with the
operating instructions "Resistance thermometer TR12 and thermocouple TC12"
(article number 14064370).
EN
1. Ex marking
DANGER!
Danger to life due to loss of explosion protection
Non-observance of these instructions and their contents may result in the
loss of explosion protection.
▶
▶
▶
Check whether the classification is suitable for the application. Observe the relevant
national regulations.
ATEX
IECEx
II 1G
Ex ia IIC T1 ... T6 Ga
II 1/2G Ex ia IIC T1 ... T6 Ga/Gb
II 2G
Ex ia IIC T1 ... T6 Gb
II 1D
Ex ia IIIC T1 ... T6 Da
II 1/2D Ex ia IIIC T1 ... T6 Da/Db
II 2D
Ex ia IIIC T1 ... T6 Db
4
Observe the safety instructions in this chapter and further explosion
instructions in these operating instructions.
Follow the requirements of the ATEX directive.
Observe the information given in the applicable type examination
certificate and the relevant regulations for installation and use in
hazardous areas (e.g. IEC 60079-11, IEC 60079-10 and IEC 60079-14).
WIKA additional information TR12/TC12, intrinsically safe designs (Ex i)