SNOW condition
4.3
1.1
To manage the alarm associated with snow, the temperature and the rain sensors must be combined.
ALARM ACTIVATED when
The measured temperature is below 2 °C
and rain has been detected (see par. 4.4)
Activation/Deactivation
of SNOW condition with P2.
RAIN sensor
4.4
1.1
ALARM ACTIVATED when
The sensitive surface of the sensor detects
drops of water.
System operation AFTER rain alarm (draining of water): once the rain alarm has ended, for the following 6 hours the control unit, upon receiving an
automatic movement command from the transmitter, will tilt the pergola slats to 33% to allow water to drain off. For 4 minutes the control unit can only execute
hold-to-run commands, thereby exiting from the alarm status.
Alarm priority
MEDIUM
What happens with ALARM ACTIVATED
The control unit tilts the slats to 66% of full opening. The control
unit only executes hold-to-run commands.
ACTIVATION
*
The motor must be
x7
stopped.
*
DEACTIVATION
The motor must be
x7
stopped.
* The buzzer will make a beep each time the button is pressed.
Alarm priority
LOW
What happens with ALARM ACTIVATED
The control unit completely CLOSES the pergola slats. The
control unit executes no command.
L4
P2
** The motors make short movements
L4
12
Factory setting
DEACTIVATED
ALARM NOT ACTIVE when
The measured temperature is above 3 °C or
rain is no longer detected.
HOLD
(5 s)
**
**
continuous
sound
Factory setting
ACTIVATED
ALARM NOT ACTIVE when
The sensor doesn't detect any drop.