Soft Start Control Output
It can be adjusted from %10 to %90 with increment and decrement buttons.
Soft Start Control Period
It can be adjusted from 1 to 100 sec with increment and decrement buttons.
PCnF ConF: Process Output Configuration Parameters
It determines output functions of Process Outputs
If Process Output is chosen Current Output, then
and
Parameter can be adjust only PID mode.
If Process Output is chosen Relay Output, then
0-20 mA Output
4-20 mA Output
It determines output functions of Process Outputs
Heating
Cooling
It determines control algorithms of Process Outputs
ON/OFF control algorithm.
PID control algorithm.
Hysteresis value of Process Outputs.
It can be adjusted from 0% to 50% of full scale.( It is active if ON/OFF control
is selected. )
It determines operation form of hysteresis
( It is active if ON/OFF control is selected.)
SV + HYS/2 and SV - HYS/2
SV and SV+HYS or SV and SV-HYS
In ON/OFF operation, this time must be passed for the output to be
energised again.It can be adjusted from 0.0 to 100.0 seconds.(It is active if
ON/OFF control is selected.)
parameter is shown
parameter is invisible.