Aln1 ConF: ALARM Output-1 Configuration Parameters
Logic Output-1
It determines logic output function for Alarm Output-1.
Alarm output
Manual /Automatic data output
Sensor break alarm output
Output is active when the process value is out of the band
which is defined with minimum value of operating scale
And maximum value of operating scale
Alarm-1 Type
It determines alarm type for Alarm-1 Output. It is active if logic output
function of Alarm Output-1 is alarm output.
Process high alarm.
Process low alarm.
Deviation high alarm.
Deviation low alarm.
Deviation band alarm.
Deviation range alarm.
Alarm- 1 hysteresis value.
It can be adjusted from 0 % to 50 % of process input scale.
(
-
is alarm output.
Alarm on delay time for Alarm Output-1.
It can be adjusted from 0 to 9999 seconds. It is active if logic output
function of Alarm Output-1 is alarm output.
Alarm off delay time for Alarm Output-1.
It can be adjusted from 0 to 9998 seconds. When the value is bigger
than 9998,
is selected. Logic output function of Output-1 if is selected as Alarm
,AoF1 parameter will be activated.
Alarm stabilisation time for Alarm Output-1.
It can be adjusted from 0 to 99 second.Logic output function of
Output-1 is selected as Alarm ,ALS1 parameter will be activated.
After the unit is power-on and Alarm Stabilisation Time is expired,
Alarm Output-1 becomes active when the alarm conditions realised
in Alt1 parameter.
) It is active if logic output function of Alarm Output-1
is seen on the screen. It means alarm latching output
13