Technical data
Power circuitry
Rated voltage U
N
Rated power DC
Rated power AC
Residual ripple U
SS
Rated frequency
Operating voltage range
Galvanic isolation between the supply circuit and
the control circuit.
Control circuit
Outputs (S11, S21)
Rated output voltage (S11 to S21)
No-load voltage (AC devices only)
Output current
Short-circuit-proof / current limiting
Inputs (S12/S33, S31/S22, S34, S35)
Rated current / peak current
(safety inputs S12/S33, S31/S22)
Rated current / peak current (reset inputs S34, S35)
Max. line resistance per channel
Permissible test pulse time t
/ test frequency
TP
Operate time t
(reset input S34)
A1
Operate time t
(reset input S35)
A2
Min. ON time t
(reset inputs S34, S35)
M
Lock time t
SP
Operate time of lock t
ASP
Recovery time t
W
Release time t
(K1, K2)
R1
Release time t
(K1, K2), switching by A1 / A2
R2
Synchronous time t
S
Output circuit
Enabling paths
Contact equipment / material
Rated switching voltage U
n
Max. continuous current I
per current path
n
Max. total current for all current
Utilization category according to EN 60947-5-1
Short circuit protection, fuse / circuit breaker
Conditional short circuit current (EN60947-5-1)
Mechanical service life (switching cycles)
General data
Clearance/creepage distance between circuits
Rated impulse withstand level
Contamination level of device: inside / outside
Rated voltage
Protection class to EN 60529 housing / terminals
Ambient / storage temperature
Weight
DC device
AC device
Terminals and connection
Single-core or finely stranded
Finely stranded with wire-end ferrule acc. to DIN
46228
AWG
Max. tightening torque
Stripping length
6
SNO 4063K / -A
12 VDC
AC/DC 24 V
AC 115 - 120 V, AC
230 V
DC 2.0 W
DC 2.0 W
-
AC 2.4 W / 4.4 VA
-
0.85 ... 1.1 x U
yes (U
= AC 115-120V, AC 230V)
N
DC 10 V
-
200 mA
Yes / –
Yes / –
80 mA / 200 mA
10 mA / 100 mA
(5 + (1,176 x UB / UN - 1) x 100) Ω
≤ 1 ms / ≤ 10 s
600 ms
–
–
200 ms (CH1 → CH2)
3 NO contacts, positively driven / Ag-alloy, gold plated
9 A² bei T
AC-15: Ue 230 V, Ie 3 A
DC-13: Ue 24 V, Ie 2,5 A
6 A class gG / melting integral < 100 A²s
-25 ... +55 / -25 ... +75 °C
1 × 0.14–2.5 mm² / 2 × 0.14–0.75 mm²
1 × 0.25–2.5 mm² / 2 × 0.25–0.5 mm²
0.5–0.6 Nm (5–7 lbf-in)
SNO 4063KM / -A
AC/DC 24 V
DC 2.1 W
AC 2.5 W / 4.6 VA
2.4 V
50 ... 60 Hz
N
DC 22 V
< 40 V
100 mA
Yes / 250 mA
40 mA / 100 mA
5 mA / 50 mA
-1
40 ms
80 ms
> 50 ms
70 ms to 130 ms
> 7 ms
≥ 100 ms
< 15 ms
< 150 ms
–
AC 230 V
6 A
= + 55 °C
A
1000 A
10x10
6
to EN 60664-1
4 kV
2 / 3
AC 300 V
IP 40 / IP 20
0.21 kg
0.25 kg
26–14
max. 7 mm