・To remove the detachable legs on site, unscrew the screws shown in the figure below. If the unit leg coating is
damaged when the detachable leg is removed, repair the coating on site.
Ⓐ
・In abnormally harsh environments such as cold and/or windy areas, sufficient countermeasures to guard against
excessive wind and snow should be taken to ensure the unit's correct operation. When the unit is expected to
operate in cooling mode in conditions under 10°C (50°F), in snowy areas, in environments subject to strong
winds or rain, install snow hoods of the following specifications (not supplied) as shown in the figure below.
Material: Galvanized steel plate 1.2T
Painting: Overall painting with polyester powder
Color: Munsell 5Y8/1 (same as the unit color)
Size: Refer to the Data Book.
Ⓒ
Ⓐ
Ⓒ
Ⓒ
Ⓑ
Ⓑ
Ⓓ
・Install the unit so that the wind will not blow directly against the inlet and outlet.
・If necessary, install the unit on a raised base of the following specifications (not supplied) to prevent damage
from snow.
Material: Angle iron (Build a structure that snow and wind can pass through.)
Height: Expected maximum snowfall plus 200 mm (7-7/8 in)
Width: Within the unit width (If the raised base is too wide, snow will accumulate on the raised base.)
・When the unit is used in a cold region and the heating operation is continuously performed for a long time when
the outside air temperature is below freezing, install a heater on the raised base or take other appropriate
measures to prevent water from freezing on the raised base.
・When installing a panel heater, provide sufficient space for maintenance accordingly. For details, refer to the
Data Book or installation manual for the panel heater.
WT08842X01
Ⓐ
Ⓒ
Ⓒ
Ⓒ
Ⓑ
Ⓑ
Ⓓ
GB-19
Ⓐ
Screws
Ⓐ
Outlet
Ⓑ
Inlet
Ⓒ
Snow hood
Ⓓ
Raised base