Before programming the control unit, check that the motor is correctly connected:
1) Cut off power supply.
2) Manually release the gate leaf, move the same at approx. half stroke and block it again.
3) Power the system again.
4) Give a step-by-step control through push-button <->.
5) The gate leaf should open.
If no movement is caused, invert the motor connections (MOT<>MOT) and limit switches SWO<>SWC.
6) Perform a complete operation, from limit switch to limit switch, without stops, to allow for the gate stroke memorisation.
The programming of the various functions of the control unit is carried out using the LCD display on the control unit and setting the
desired values in the programming menus described below.
The parameters menu allows you to assign a numerical value to a function, in the same way as a regulating trimmer.
The logic menu allows you to activate or deactivate a function, in the same way as setting a dip-switch.
Other special functions follow the parameters and logic menus and may vary depending on the type of control unit or the software
release.
USE oF PRoGRAmmiNG KEYS
Press <PG> key to gain access to the Main Menu. These keys can be selected by pressing + and – keys.
• If <+> is pressed, the Function Menu can be scrolled from top to bottom.
• If <-> is pressed, the Function Menu can be scrolled from bottom to top.
• If <PG> key is pressed, presetting to be modified can be entered.
• The preset values can be modified by using <+> and <-> keys.
• The value is programmed if <PG> key is pressed again. The word "PRG" appears on the display.
See paragraph "Programming Example".
NoTES:
Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without making any chan-
ges.
If the push-button <-> is pressed with display off, this is like giving a step-by-step control.
When the board is switched on, the software version is displayed for around 5 sec
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
After waiting 30s the control unit quits programming mode and switches off the display.
In the tables hereunder the single functions available in the control unit are shown.
mENU
Automatic closure time. It is activated only with "TCA"=ON logic.
TCA
At the end of the preset time, the control unit controls a closure operation.
Operating time. The operating time is adjusted at normal speed during motor opening and
TM
closing phases.
Tped
The area covered by the gate during its partial opening movement (pedestrian) is adjusted.
The area covered by the gate during the braking phase is adjusted.
Tsm
0 = braking disabled
PMo
The torque applied to the motor in the opening phase is adjusted.*
PMC
The torque applied to the motor in the closing phase is adjusted *.
Pso
The torque applied to the motor during braking in the closing phase is adjusted.*
Psc
The torque applied to the motor during braking in the opening phase is adjusted *
The intervention threshold of the anti-crashing device (Encoder) during the phase at normal
SeaU
speed is adjusted.*
99:maximum sensitivity - 0: minimum sensitivity
14
Common for limit switches.
Connection of secondary winding of 24V transformer
Motor connection, 230Vac – single phase:
M1-Phase/ COM-Common/ M2-Phase
Connection to capacitor
Connection to flashing light, 230Vac 40W max.
Connection to transformer primary winding
To ChECK CoNNECTioNS
PRoGRAmmiNG
PARAmETERS, LoGiCS ANd SPECiAL FUNCTioNS
PARAMETERS (PAR)
FUNCTioN
miN-mAX-
mEmo
(default)
1-240-(40s)
1-250-(90s)
20-250-(50
cm)
0-250-(0 cm)
1-99-(40%)
1-99-(40%)
1-99-(50%)
1-99-(50%)
0-99-(0%)