10. ALERT Emergency messages button and indicator. 
Press  it,  in  emergency  mode,  to  activate  ALERT  message.  Green  if  ALERT  message  is  being 
broadcast. Yellow if failure is detected in ALERT message. Extinguish in normal status. 
11. Line input Selector switch. 
Selector of the local input which will be broadcasted as BGM in the own unit. 
12. All zone selector. 
Press it to activate the 6 zones of the unit at the same time. It does not affect other units. 
13. Zone fault indicator. 
It lights on in Yellow when open or short circuit is detected in lines A or B. 
14. Zone paging indicator. 
It lights on in green when PAGING  is working, either from Emergency Microphone or Remote 
microphone. 
15. Zone EVAC ALERT Broadcast Indicator. 
It lights on in red when EVAC or ALERT emergency broadcast is working. 
16. Zone Background Music Indicator. 
It  lights  on  in  green  when  zone  is  selected  for  music  broadcast.  In  emergency  mode  it  also 
indicates the zone is selected for message broadcasting. 
17. Zone Selector. 
Button to individually activate or deactivate the output zone. It is used for BGM and emergency 
messages. 
18. Zone Output Attenuator. 
Increase or decrease the individual zone speaker volume. It has 6 attenuation levels, from 0dB 
to ‐15dB. It does not affect in Emergency mode 
19. Emergency Microphone Input. 
Input connector for the emergency microphone. 
20. Monitor Speaker Attenuator. 
Increase or decrease the built‐in monitor speaker volume. 
21. Emergency Microphone Gain Control. 
It is used to adjust the emergency microphone input sensitivity. 
22. Treble Control. 
Increase or decrease the overall treble output. 
23. Bass Control. 
Increase or decrease the overall bass output. 
24. Master Volume Control. 
General  volume  control,  it  does  not  affect  emergency  messages  or  live  messages  from  
NOVA‐12RM. 
 