8. Technical specifications

MultiPlus
PowerControl / PowerAssist
AC input
Maximum feed through current (A)
Minimum AC supply current
capacity for PowerAssist (A)
INVERTER
Input v oltage range (V DC)
Output
(1)
Cont. output power at 25 °C (VA)
Cont. output power at 25 °C (W)
Cont. output power at 40 °C (W)
Peak power (W)
Maximum ef f iciency (%)
Zero-load power (W)
CHARGER
AC Input
Charge v oltage 'absorption' (V DC)
Charge v oltage 'f loat' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary output
Multi purpose relay
(5)
Protection
(2)
VE.Bus communication port
General purpose comm. port
Common Characteristics
ENCLOSURE
Common Characteristics
Battery -connection
230 V AC-connections
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Saf ety
Emission / Immunity
1) Can be adjusted to 60Hz; 120V 60Hz on request
2) Protection
a. Output short circuit
b. Ov erload
c. Battery v oltage too high
d. Battery v oltage too low
e. Temperature too high
f . 230VAC on inv erter output
g. Input v oltage ripple too high
3) Non linear load, crest f actor 3:1
4) At 25 °C ambient
5) Programmable relay which can be set f or general
DC underv oltage or genset start signal f unction
AC rating: 230V/4A
DC rating: 4A up to 35VDC, 1A up to 60VDC
26
12/5000/200-100 230V
Input v oltage range: 187-265 VAC
9,5 – 17
Output v oltage: 230 VAC ± 2%
5000
(3)
4500
4000
10000
94
25
Input v oltage range: 187-265 VAC
14,4
13,8
13,2
200
(4)
4
Max. 50A Switches of f when no external AC source av ailable
For parallel and three phase operation, remote monitoring and sy stem integration
Material & Colour: aluminium (blue RAL 5012)
24/5000/120-100 230V
Y es
Input f requency : 45 – 65 Hz
100
6,3
19 – 33
5000
4500
4000
10000
94
25
Input f requency : 45 – 55 Hz
Power f actor: 1
28,8
27,6
26,4
120
4
Y es
Y es, 3x
a - g
Y es, 2x
Operating temp.: -20 to +50°C (f an assisted cooling)
Humidity (non condensing) : max 95%
M8 bolts (2 plus and 2 minus connections)
M6 bolts
30
444 x 328 x 240
EN 60335-1, EN 60335-2-29
EN55014-1, EN 55014-2, EN 61000-3-3
48/5000/70-100 230V
38 – 66
Frequency
50 Hz ± 0,1%
:
5000
4500
4000
10000
95
25
57,6
55,2
52,8
70
Protection category : IP 21