Technical Data - D+H CDC 200/600 Manual Original

Ocultar thumbs Ver también para CDC 200/600:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Technical Data

Type
Rated voltage
Chain type
Nominal pressure
Nominal locking force
Service life
Housing
Protective system
Temp.range
Fire stability
/
Stroke lenght * **
Additional functions **
* Adjustable with PLP 1
Running speed and forces
Normal operation
SHEV-fast running =
CDC 200/600:
= 200 N,
6,7 mm/s
=
200 N,
11,4 mm/s
CDC 200/600-SBD:
= 150 N,
6,7 mm/s
=
150 N,
11,4 mm/s
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing ranges 3 and 2, the drive runs
"OPEN" for 10 seconds, then "CLOSE" again. If
closing is not possible after three attempts, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closing range 2 and
1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing edges.
Danger of crushing hands and fingers!
6/16
CDC 200/600 (-SBD)
CDC 200/600
24 VDC, ±15%, 1,0 A
Standard chain
200 N
approx. 1500 N
>10.000 double strokes
Aluminium die-casting
IP 50
-5 ... +75°C
30 min / 300°C
max. 600 mm
Active closing edge protection = deactivated
Locking relief = activated (Retraction lift max. 0,2 mm)
** Programmable with PLP 1 and PDA Servicetool
=
All forces + approx. 20 %
switch-off reserve (temporary)
CDC 200/600 -SBD
24 VDC, ±15%, 0,83 A
Side bow chain
150 N
English
Beside -
closing edge
99.823.42 2.2/09/13

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cdc 200/600-sbd

Tabla de contenido