6. Failure Messages in ESM 3721HT Hatcher Controller
1-
Screen Blinking Temperature Sensor failure . Sensor connection is wrong or there is no sensor
connection. While this message shown on this display, if buzzer function selection
internal buzzer starts to operate.
2- Self Tune temperature error.
temperature read from the sensor is closer to the Process Set value than 5% of the scale Self tune
operation is not allowed.
7. Manual Start of Egg Tray Rotator Operation with Engine Button
START
STOP
8. Self Tune Method
Self Tune method is used for determining PID parameters used by the device.
Starting Self Tune (Step Response Tuning) Operation by the user :
• Adjust temperature control on/off or PID parameter
• Adjust self tune selection parameter (
• "Tune" and temperature are displayed alternately on the main operation screen.
In this way the Self-Tune process will be started
If Self Tune operation is finished without any problem, the device saves the new
PID coefficients to memory and continue to run.
parameter is adjusted
Not:
The temperature value read from the sensor must be less than 5% of the process set
value in order to start the self tune operation.
Cancelling Self Tune(Step Response Tuning) operation :
1 - If sensor breaks;
2 - If auto tune operation can not be completed in 8 hours ;
3 - If user adjusts
4- During self tune operation if the user changes the temperature control from pid to on/off;
5 - If process set value is changed while self tune operation is being performed;
Self tune is canceled. "Tune" is not displayed. Then, without doing any changes in PID
parameters, device continues to run with previous PID parameters.
Appears on the main screen.this fault occurs when the
While button protection parameter value is
main operation screen if engine button is pressed, manual
PAUSE
engine start will be active.When the button is released the
ü
ü
ü
engine start will be passive and engine stops.
=
automatically.