FCW installation (water
cooling system)
If the Granizadora Digital you
bought is endowed with the
water cooling system, it is
necessary to follow these
instructions.
On the machine front side
(outlet side)
There are some water exit (left)
and entrance pipes (right) as
shown in the pic. f .
The quantity of water
necessary for the functioning
can change according to the
product cooling phases, with
higher values when starting the
slush production and values
that are close to zero when you
want to keep the slush. We
therefore recommend to
connect the machine to the
water network with the
maximum capacity, thus the
pressure switch valve (pic. g) in
the machine will regulate the
flux according the real
necessity.
Important:
It is not possible to connect the
FCW water entrance with the
input of another machine based
on a water cooling system
(series).
It is not possible to connect
several machines based on the
water cooling system on the
same outlet.
Pressure switch refit
procedure
When the pressure switch light,
near main switch in ON,
Pressure switch light
this indicates that the pressure
switch intervened to deactivate
the compressor. In order to refit
this device, it is important to
follow the instructions below:
1°
Disconnect the power
cable.
2° Unscrew the crossed screws
at the bottom of the right
side panel from the side of
the condenser.
- 27 -
3° Slip the panel.
4° Press the button on the
pressure switch.
5° Close the panel and turn on
the machine again.