For safe installation of 9410 the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
9410 Power Control Unit
IECEx Certificate
Marking:
Standards:
Non Hazardous Area or Zone 2
T4: -20 ºC <Ta < +60ºC
91 92 93 94 95
Status
24 V
GND
Revision date:
2012-06-27

IECEx Installation drawing

IECEx KEM 08.0025 X
Ex nA nC IIC T4 Gc
IEC60079-0:2011, IEC60079-15:2010
34
Backup -
33
Backup +
32
Supply +
31
Supply -
14
13
NC
12
COM
11
NO
9410
Power
Version Revision
V3R0
9410 - Versión del producto 9410-001
WWW.PRELECTRONICS.COM
Terminal 34-33
Backup: 21.6 VDC – 26.6 VDC / 4 ADC
Terminal 31-32
Supply: 21.6 VDC – 26.6 VDC / 4 ADC
Terminal 11, 12, 13
Power Rail Status Relay
Unclassified installation
250 VAC, 2 A, 500 VA / 30 VDC, 2 A, 60 W
Zone 2 installation:
32 VAC, 2 A, 64 VA / 30 VDC, 2 A, 60 W