[Fig. 3.2.1]
Nut (not supplied)
Double nut (not supplied)
Hanging bolt ø10 (M10 screw) (not supplied)
Washer (with cushion) (supplied)
* Attach the cushion facing down.
Minimum 30 mm
Washer (without cushion) (supplied)
[Fig. 3.2.2]
Within 1.5º
Drain socket
Viewed from the front of the control box
[Fig. 3.2.3]
4
[Fig. 4.1.1]
4
CMB-M104, 106, 108V-J1(-TR),
CMB-M104, 108V-KB1(-TR)
14
(Top view)
<Ⓒ>
Within 200 mm
BC controller
Ceiling void
Ceiling
50
20
3.2
CMB-M1012, 1016V-J1(-TR)
CMB-M108, 1012, 1016V-JA1(-TR)
CMB-P1016V-KA1(-TR)
30
Viewed from the drain socket side
4.1
Indoor unit connecting port
Cutting point : ø9.52 (Liquid side) or ø15.88 (Gas side)
(Indoor unit model : above P/M50)
Cutting point : ø6.35 (Liquid side) or ø12.7 (Gas side)
(Indoor unit model : P/M50 or below)
Cut the piping at the cutting point
Have pipe expansion of indoor unit connecting port
Field pipe
Note:
Remove burr after cutting the piping to prevent entering the piping.
Check that there is no crack at the pipe expansion part.
<Ⓓ>