External power supply kit
1
Safety
Danger!
Live components and stripped cable!
Risk of injury from electric shock. The system must be current-free during connection work.
Danger!
Do not install and operate the system at a height over 2000 m above sea level. Risk of injury
from electric shock.
Caution!
EN 62368-1: MS 3. The installation height is recommended to a maximum of 2 m.
!
Notice!
i
IP30 conformity
If you break out the pre-cut cable entry points, ensure that the IP30 conformity is still
established, e.g. by using cable glands.
Notice!
i
Adhere to your national and local guidelines.
2
Short information
The FPP‑5000 external power supply kit is designed for universal power supply, and has space
for two batteries (e.g. 12 V/45 Ah).
The following extensions must be ordered separately:
–
–
3
Installation
Notice!
For detailed information on installation steps for the frame and housing, refer to the quick
i
installation guide of mounting frames FMH 0000 A, FBH 0000 A, FSH 0000 A with document
number 4.998.153.998, and quick installation guide of housing PMF 0002 A with document
number F.01U.003.689.
Bosch Sicherheitssysteme GmbH
FPP-5000-TI Trouble interface, provides the fault message transfer of the mains fault
signal and the battery fault signal to the fire panel
FPP-5000-TI13 Communication interface, transmits the following faults to the fire panel:
–
Mains fault
–
Battery fault
–
Battery internal resistance fault
–
BCM-0000-B Battery Controller Module fault
–
Short 24 V outputs; current threshold values for detection of creeping shorts have to
be configured via the Remote Programming Software (RPS)
–
Ground fault
Installation manual
Safety | en
17
2021.04 | 8.0 | F.01U.005.065