Minimum Humidity Set Value Parameter (Default = Minimum Value of Device Scale)
Humidity
set value can not be lower than this value. This parameter value can be adjusted
from minimum value of device scale to maximum
Maximum Humidity Set Value Parameter (Default = Maximum Value of Device Scale)
Humidity set value can not be greater than this value.
adjusted from minimum humidity set value parameter
device scale.
Humidity Sensor Offset Parameter ( Default = 0.0 )
From -10 to 10%RH for Humidity Sensor (0%RH-100%RH)
From -10.0 to 10.0%RH for Humidity Sensor (0.0%RH-100.0%RH)
Temperature Alarm Function Selection Parameter
Temperature Alarm is inactive.
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Note : If this parameter is select 0, Temperature Alarm parameters
will be not observed.
Temperature Alarm Set Parameter
This parameter value can be programmed between temperature minimum alarm set
parameter and temperature alarm set maximum
Temperature Alarm
This parameter value can be adjusted form 0 to %50 of the device scale.
Alarm
Set Minimum Parameter (Default = Minimum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from minimum value of
device scale to temperature alarm set maximum parameter value.
Alarm
Set Maximum Parameter ( Default = Maximum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from temperature
alarm set value parameter
Temperature Alarm On Delay Time Parameter
Temperature Alarm On Delay Time can be defined with this parameter. It can be
adjusted from 0 to 99 minutes.
Temperature Alarm Delay After Power On Parameter
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm.
Humidity Alarm Function Selection Parameter
Humidity Alarm is inactive.
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Note : If this parameter is select 0, Humidity Alarm parameters
will be not observed.
( Default = 50.0 °C )
Hysteresis
Parameter
to maximum value of the device scale.
It can be adjusted from 0 to 99 minutes.
Humidity
set value parameter
This parameter value can be
to maximum value of the
( Default = 0 )
,
,
parameter.
( Default = 0)
( Default = 0)
( Default = 0)
( Default = 0 )
,
,
,
,
,
and
,
and
11