Technical Data - ABB IMB 36 - 765 Guía Para El Comprador

Transformadores de medida exteriores
Tabla de contenido

Publicidad

PQSensor™

Technical data

Absolute gain error
Gain stability over operating temperature range,
at operating frequency, (measured at "Diff Output"
with 75 Ω termination)
Gain stability over operating temperature range,
at operating frequency, (measured at the integral
output with 75 Ω termination)
Frequency response
Frequency response measured of "Diff Output"
Frequency response of "Output"
Phase error
Maximum burden
Output current levels
Operating temperature range
Power supply input voltage
Size
Outdoor specification
European Patent Number: EP 1295133. US Patent Number: US 6,919,717.
62 Transformadores de medida exteriores | Guía para el comprador
0.5% at operating frequency, measured at either outputs into 75 Ω terminations.
0.3% of full-scale output.
0.4% of full scale output. This does not include any effects of the CVT.
5 Hz up to 20 kHz
− 0.17 dB max at 5 kHz with respect to gain at operating frequency.
− 0.25 dB max. It will not have DC response.
Less than 1.5 degrees at 3 kHz and less than 3 degrees at 5 kHz. Improved phase response is
offered on request for special applications
150 Ω pure resistive. This corresponds to a maximum voltage at the measurement device (e.g.
power quality monitor) of 3 V rms at a current of 20 mA. The burden may be selected to be any
value up to the maximum to suit the measurement device (the monitor). All figures related to
accuracy and error mentioned in this document would also apply for burdens up the maximum
values.
Differential current output of 20 mA rms, driving 75 Ω through 300 meters of cable.
Cable capacitance is typically 100 pF/m.
-40 to +55 °C
48 V dc ±10% or 85-260 V dc/ac ±10%.
The unit can be supplied from the CVT nominal output of 69 V ac. Power consumption 200 mW.
Signal conditioning module: 10.2 x 6.3 x 3.6 inches (260 x 160 x 92 mm).
Current transformers: outer and inside diameters of 2 inches (50 mm) and .8 inches (20 mm), a
depth of .8 inches (20 mm).
Conform to IP 65.

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Emf 52 - 170Cpb 72,5 - 765Cca 72 - 550Ccb 145 - 765

Tabla de contenido