AC power source installed and grounded/bonded in accordance with ABYC standards
◆
Control wires connected to terminal strip with fork or ring terminals
◆
Circuit breakers sized according to specifications on the data plate label
◆
Pump Relay Panel (if used) has a dedicated circuit breaker sized for the pump but not to
◆
exceed 20 amps maximum.
3.15.4 Grilles and Ducting
Supply air grille mounted as high as possible
◆
Return air grille mounted as low and as close to the a/c unit as possible
◆
Return air grille mounted away from bilge vapors or exhaust fumes
◆
Ducting is pulled taut, straight, smooth and properly connected with no excess
◆
3.15.5 Quick Start Operations Checklist
Ensure seawater intake ball valve (sea cock) is open.
◆
Turn on the a/c circuit breaker. If the seawater pump has its own circuit breaker, make sure to
◆
turn it on.
Turn the system on. Set the desired cabin temperature (set point).
◆
Check for a steady solid stream of water from the overboard discharge.
◆
Verify that there is steady airflow out of the supply air grille
◆
If the unit does not appear to be operating properly, refer to troubleshooting guidelines.
◆
Note: Do not turn the unit off and immediately turn it back on. Allow at least 30 seconds for
refrigerant pressure equalization.
3.16 Wiring Diagrams
WIRING DIAGRAM GIA-MAB-O-05Y01, GIA-MAB-O-09Y01 The
specification of power cord is AWG14*3(3*1.5)