Hysteresis Parameter for Temperature ( Default = 0.1 °C )
From 1 to 10°C for NTC,PTC, PT-100 (0°C, 100°C) ,From 1 to 18°F for NTC,PTC ,PT-100
(32°F, 212°F),From 0.1 to 10.0°C for NTC, PTC, PT-100 (0.0°C,100.0°C), From 0.1 to
18.0°F for NTC, PTC, PT-100 (32.0°F,212.0°F) ,From 1 to 10°C for ProNem Mini PMI-P
(-20°C, 80°C) ,From 1 to 18°F for ProNem Mini PMI-P (-4°F,176°F), From 0.1 to 10.0°C for
ProNem Mini PMI-P (-20.0°C,80.0°C), From 0.1 to 18.0°F for ProNem Mini PMI-P
(-4.0°F,176.0°F).
In ON/OFF control algorithm, temperature
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value's oscillation period or amplitude around
set value changes according to controlled
system. For reducing oscillation period of
temperature value, a threshold zone is formed
below or around set value and this zone is
named hysteresis.
Minimum Temperature Set Value Parameter ( Default = 10.0°C)
Temperature set value can not be lower than this value. This parameter value can be
adjusted from minimum value of device scale to maximum temperature set value
parameter
Maximum Temperature Set Value Parameter ( Default = 40.0 °C )
Temperature set value can not be greater than this value.
This parameter value can be adjusted from minimum temperature set value parameter
to maximum value of the device scale.
Temperature Sensor Offset Parameter ( Default = 0 )
From -10 to 10°C , NTC,PTC , PT-100 (0°C, 100°C)
From -18 to 18°F, NTC,PTC , PT-100 (32°F, 212°F)
From -10.0 to 10.0°C , NTC ,PTC , PT-100 (0.0°C,100.0°C)
From -18.0 to18.0°F NTC, PTC , PT-100 (32.0°F,212.0°F)
From -10 to 10°C ,ProNem Mini PMI-P ( -20°C, 80°C )
From -18 to 18°F,ProNem Mini PMI-P ( -4°F, 176°F )
From -10.0 to 10.0°C, ProNem Mini PMI-P ( -20.0°C, 80.0°C )
From -18.0 to18.0°F, ProNem Mini PMI-P ( -4.0°F,176.0°F )
Humidity Sensor Scale Selection Parameter ( Default = 0 )
Analogue input range is determined with this parameter.
(1)
Z or
0..10V
(1)
Z or
2..10V
Note :
parameter ProNem Mini PMI- type device are not observed.
Hysteresis Parameter for Humidity ( Default = 1 )
From 1 to 10 for Humidity Sensor (0%RH, 100%RH)
From 0.1to 10.0 for Humidity Sensor (0.0%RH,100.0%RH)
In ON/OFF control algorithm,
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value's oscillation period or amplitude
around set value changes according to
controlled system. For reducing oscillation
period of temperature value, a threshold
zone is formed below or around set value
Temperature
(2)
Z
0..20mA
(2)
Z
4..20mA
P
Humidity
Humidity
Control
Output
thSt
Set
Control
Output
ON
OFF
hhSt
Set
ON
thSt
Time
Time
hhSt
Time
Time
10