Temperature Alarm Function Selection Parameter
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Temperature Alarm Set Parameter
This parameter value can be programmed between temperature minimum alarm set
parameter and temperature alarm set maximum
Temperature Alarm
This parameter value can be adjusted form 0 to %50 of the device scale.
Alarm
Set Minimum Parameter (Default = Minimum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from minimum value of
device scale to temperature alarm set maximum parameter value.
Alarm
Set Maximum Parameter ( Default = Maximum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from temperature
alarm set value parameter
Temperature Alarm On Delay Time Parameter
Temperature Alarm On Delay Time can be defined with this parameter. It can be
adjusted from 0 to 99 minutes.
Temperature Alarm Delay After Power On Parameter
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm.
It can be adjusted from 0 to 99 minutes.
Humidity Alarm Function Selection Parameter
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Humidity
Alarm Set Parameter
This parameter value can be programmed between humidity minimum alarm set
parameter and humidity alarm set maximum
Humidity Alarm
Hysteresis
This parameter value can be adjusted form 0 to %50 of the device scale.
Humidity
Alarm
Set Minimum Parameter(Default =Minimum Value of Device Scale)
if humidity alarm is active, this parameter value can be adjusted from minimum value of
device scale to humidty alarm set maximum parameter value.
Humidity
Alarm
Set Maximum Parameter(Default =Maximum Value of Device Scale)
if humidity alarm is active, this parameter value can be adjusted from humidity alarm set
minimum parameter
Humidity
Alarm On Delay Time Parameter
Humidity
Alarm On Delay Time can be defined with this parameter. It can be adjusted
from 0 to 99 minutes.
Humidity
Alarm Delay After Power On Parameter
When power is first applied to the device, this time delay must be expired for activation of
Humidity alarm.
It can be adjusted from 0 to 99 minutes.
( Default = 50.0 °C )
Hysteresis
Parameter
to maximum value of the device scale.
( Default = 50 )
Parameter
( Default = 0)
to maximum value of the device scale.
( Default = 1 )
parameter.
( Default = 0)
( Default = 0)
( Default = 0)
( Default = 0 )
parameter.
(Default = 0)
(Default = 0)
12