Buzzer Function Selection
Buzzer is inactive.
Buzzer is active during temperature alarm
Buzzer is active during humidity alarm
Buzzer is active during Temperature sensor failures.
Buzzer is active during Humidity sensor failures.
Buzzer is active during Temperature sensor failures or temperature alarm.
Buzzer is active during Humidity sensor failures or Humidity alarm.
Buzzer is active during Temperature sensor failures or Humidity sensor failures
Buzzer is active during Temperature sensor failures or Humidity sensor failures
or temperature alarm or humidity alarm.
Buzzer Active Time
( Default =
If buzzer function selection parameter
Buzzer active time can be define with this parameter. It can be adjusted from 1 to 99
minutes. When this parameter is 1, if decrement button is pressed,
this condition buzzer is active till buzzer silence button is pressed.
Button Protection Parameter
There is no protection.
Temperature set value can not be changed.
Humidity set value can not be changed.
Manual engine start is not available.
Humidity set value and Temperature set value can not be changed
Humidity set value can not be change and Manual engine start is not available.
Temperature set value can not be change and Manual engine start is not
available.
Temperature set value and Humidity set value can not be changed. Also
Manual engine start is not available.
Programming Mode Accessing Password
It is used for accessing to programming mode. It can be adjusted from 0 to 9999. If it is 0,
password is not entered for accessing to the parameters. When the password screen is not
set as "12" , If the user enters '12' in password screen
accessed and they can changed.
Parameter( Default = 0 )
)
value
( Default = 0 )
( Default = 0 )
= 0, this parameter is not observed.
and
parameters are
is observed. In
13