Connect battery line, be careful with positive and negative charges. Positive battery line
f.
first, then negative battery line.
g. Tighten all bolts on each part of generator.
h. Before starting, main circuit breaker on 'BREAK' position.
After all above check lists, start the generator to have a try, before loading start, still need
i.
check if phase line same as local electric phase, if everything OK, loading working is
accepted.
PANEL KEYS
Key
Definition
Manual/Decrease
Auto/Increase
Page/Confirm
Alarm Indicator
Pressing this button will start the generator manually and
place it into its manual mode; in settings menu moves
cursor down an decreases the set value.
Pressing this button will place the module into its auto
mode; in settings menu moves cursor up and increases
the set value
Pressing this button in any situation will shut down the
Stop
generator and place it into its standby mode; in case of
alarm, pressing this button will clear alarms
Turn
Using this button you can scroll pages of the LCD monitor;
in settings menu press to move cursor and confirm
This indicator will flash when an alarm occurs
Description