Manual Start; Auto Mode; Stop Mode - TOYAMA TDMLG4004-T9C Manual De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

OPERATION
The module has three working modes:
Manual Mode(
) ,Auto Model(
) and Stop Mode(
).

MANUAL START

After pressing Manual Start button and holding it for at least one second, the indicator next to
the button will be illuminated, Preheating output will be activated firstly and preheat delay begins.
One second before it is finished, fuel output will be activated for one second and after that
preheat output will be deactivated; starter is energized to output and engine cranks. When
generator frequency reaches the pre-set value, the starter motor will be deactivated and
generator will start. Then, safety delay will start, after it is finished, idle delay will start and when
it is finished idle relay will be closed and the generator will start working at normal speed.

AUTO MODE

After pressing and holding button for at least one second, the indicator next to the button will
be illuminated and the module will be placed into its automatic mode. If remote start signal is
active(remote start input port is connected to B-), after start delay the genset will start.
Preheating output will be activated firstly and preheat delay begins. One second before it is
finished, fuel output will be activated for one second and after that preheat output will be
deactivated; then starter is energized to output ( engine will try to start according to the pre-set
number of times; if one of the attempts is successful, the start process will be completed,
otherwise fail to start alarm will be initiated: fail to start indicator on the panel will be illuminated
and common alarm indicator will flash). After start delay and idle delay, idle replay will be
deactivated and the generator will start working at normal speed.
NOTE: During crank rest time, fuel output is deactivated; three seconds after the beginning of
the delay, preheat and ETS outputs will be activated; after the end of the delay, ETS output will
be deactivated and fuel replay output; preheat output will be deactivated before the beginning
of crank.
When remote start signal is deactivated, after stop delay, the generator enters idle state and
the idle relay is deactivated. After idle delay, fuel replay deactivates, ETS relay output activates,
and the genset automatically stops. After complete stop, EYS relay deactivates.

STOP MODE

After pressing and holding for at least one second during normal operation of the genset ( in
manual or auto modes), the light indicator near the button will be illuminated and idle operation
will begin. When idle relay deactivates and after idle delay, fuel relay is deactivated and ETS
output is energized. When complete stop of the generator, ETS is deactivated.
In case of fault alarm, pressing and holding the button for one second will clear alarms. Holding
it for more than one second will illuminate all indicators on the panel (light test function).
Pressing this button for more than one second in stop mode will lead to activation of ETS output
and illumination of all the indicators on the panel(light test function). Releasing the button will
immediately deactivate ETS output and light test function.
When in stop mode, the module will only react to emergency stop signal.
NOTE: Configurable output ports can be set as one of the following functions: 'ETS output' 'Idle
output' or 'preheat output' via PC. There for, all three functions cannot be active at the same
time; the above-mentioned is only to describe the logical course of action of the controller in

Publicidad

Tabla de contenido
loading

Tabla de contenido