Turn off and let the appliance cool before servicing. Only a qualified service person
WARNING
should service and repair the appliance.
Problem
Appliance is smoking/
sooting excessively
Note: It is natural
and unavoidable
for vented gas log
sets to create some
level of soot where
flames contact the
logs.
Burner is overly
noisy.
Note: The
combustion of
gas creates a low
level of noise that
cannot be avoided.
Burner flame is too
high or too low.
Appliance produces a
clicking/ticking noise
just after the burner is
lit or shut off.
©2017 Pinnacle Climate Technologies
Troubleshooting Guide
Possible Cause
1. Poor fuel quality
2. Fireplace venting system not
drafting properly
3. Excessive flame impingement
or blockage
4. Improper fuel/air mixture
5. Excessive gas supply/pressure
6. Damper closed or not open
sufficiently
1. Passage of air/gas across
irregular surfaces
1. Incorrect gas supply or pressure
2. Blocked burner orifice or burner
manifold ports
3. Wrong burner orifice size
4. Valve not operating properly
5. High altitude
1. Metal expanding while
heating or contracting while
cooling
1. Contact local natural gas company.
2. Adjust damper wide open and/or have fireplace
and venting professional cleaned and checked.
3. Separate the logs to allow more flame passage.
4. Remove any foreign items from the flame pattern.
5. Preheat flue in very cold weather.
6. Open the damper fully when operating the
gas log set.
1. Fix any tight bends or kinks in gas supply line.
1. Check for proper gas supply pressure.
2. Free burner orifice and manifold ports of any
burrs, paint, or other blockage.
3. Verify correct burner orifice sizing.
4. Replace valve.
5. Adjust orifice size for altitude.
1. This is typical with most appliances of this
sort. If the noise is excessive, contact a quali-
fied service person.
17
Vented Gas Log Appliance User's Manual
Solution