Technical data
Supply
Nominal voltage U
N
Rated power DC
Residual ripple U
SS
Control circuits
Internal operating voltage S11/S33, used only for the supply of the
inputs S34, S35, S12, S31, S22
Response time / recovery time of fuse (PTC resistor)
Rated current / peak current S12
Rated current / peak current S31, S22
Rated current / peak current S34, S35
Response time t
(with reset button monitoring)
A1
Response time t
(without reset button monitoring)
A2
Release time t
K1, K2
R1
Off-delay time t
K3, K4 (2 ranges, adjustable)
R2
Off-delay time t
K3, K4 (adjustable only SNV 4063KL-107, without BG
R2
approval)
Min. ON-time t
S33-S34
M
Min. ON-time t
S33-S35
M
Recovery time t
Start
W
Synchronous monitoring time t
Output circuits
Contacts
Switching voltage U
n
Max. rated current I
per current path
n
Max. total current for all current paths
Application category according to EN 60947-5-1
Short-circuit protection, fuse element type gG max.
General data
Creepage and clearance
Rated withstand voltage
Contamination level: internal/external
Test voltage
Protection degree Housing / Terminals acc. to
Ambient temperature working range / storage range
Weight
Terminals and connection
Single-core or finely stranded
Stripping length
Finely stranded with wire-end ferrule to DIN 46228
Max. tightening torque
6
S
EN 60529
min.
typ.
DC 20.4 V
DC 24 V
2.6 W
DC 22 V
2 s / 3 s
25 mA / 50 mA
25 mA / 100 mA
40 mA / 50 mA
30 ms
700 ms
25 ms
0.15 s ±16%
1.5 s ±16%
7.5 s ±25%
200 ms
200 ms
100 ms
2 NO enabling current paths, non-delayed, positively driven
1 NO enabling current paths, off-delayed, positively driven
AC 230 V
12 A
non-delayed
AC-15: Ue AC 230 V, Ie 4 A
DC-13: Ue DC 24 V, Ie 3 A
acc. EN 60664-1
4 kV
2 / 3
AC 300 V
IP 40 / IP 20
-25 ... +55 / -25 ... +75 °C
0,2 kg
screw-type terminals
1 x 0.2 - 2.5 mm² /
2 x 0.2 - 0.75 mm²
max. 8 mm
1 x 0.25 - 2.5 mm² /
2 x 0.25 - 0.5 mm²
0.5 to 0.6 Nm
max.
DC 26.4 V
2.4 V
3 s ±16%
30 s ±16%
150 s ±25%
3 s
500 ms
500 ms
6 A
delayed
AC-15: Ue AC 230 V, Ie 3 A
DC-13: Ue DC 24 V, Ie 3 A
6 A
spring-type terminals
2 x 0.2 - 1.5 mm²
2 x 0.25 - 1.5 mm² (trapezoid
crimping)
---