Vaisala Indigo500 Serie Guía Rápida página 19

Ocultar thumbs Ver también para Indigo500 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 91
+
CH1
RS-485
PROBE
1
+
CH2
24 VOUT
+
ANALOG
CH3
INPUT
+
CH4
1
Table 9 Connection terminals for probe 1 and probe 2
Terminal
Function
RS-485-
RS-485-
RS-485+
RS-485+
24 VOUT -
Power GND and
RS-485 common
24 VOUT +
Positive supply voltage to
probe
Verifying tightness of cable glands
To maintain enclosure tightness and provide strain relief to the cables, all cable glands must be
tightened. Unused cable glands must remain plugged.
1. Check every cable gland that is in use:
a. Pull on the cable to verify that the cable is securely held by the cable gland.
b. Tighten the cable gland if the cable moves.
2. Check that every unused cable gland is plugged and tightened.
VS
2
2
White
Black
Blue
Brown
For the M16×1.5 cable glands ordered
together with the transmitter from Vaisala,
the cable diameter is 2.0 ... 6.0 mm
(0.08 ... 0.24 in). Tightening torque for the
cable gland is 6 Nm.
The recommended maximum length of the
probe cable is 30 m (98 ft).
1
Probe 1 lead-through, M16×1.5
2
Probe 2 lead-through, M16×1.5
Wire color in Vaisala
Notes
cables
Max. wire size: 2.5 mm
(14 AWG)
2
17

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Indigo520

Tabla de contenido