Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

2
LPG kit
2.1

Kit description

The kit allows the burners RS 190 and RS 190/M designed to
work with natural gas to burn LPG.
The kit is composed of:
Description
Distributor assembly
Rings
Interior tube
(for short combustion head version)
Interior tube
(for long combustion head version)
Label
Instruction
2.2

Technical features

Burner
Burner output
Minimum gas pressure
Fuel
2.3
Conversion
Proceed as follows:
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
2915572
Quantity
1
2
1
1
1
1
RS 190 - RS 190/M
465 ÷ 2290 kW
400.000 ÷ 1.970.000 kcal/h
Maximum capacity requires 30 mbar measured on the pipe coupling, with 0 mbar resistance in the com-
bustion chamber and gas with net calorific value of 22.200 kcal/Nm
Commercial LPG (C
H
= 93 - 94%)
3
8
Net calorific value = 25.8 kWh/Nm
D1257
LPG kit
Apply the self-adhesive label for LPG operation
near the characteristics label.
WARNING
Before starting the kit installation operations, get a
suitable lifting system ready.
Be careful as some drops of fuel may leak out dur-
ing the kit installation phase.
Tab. A
3
3
- 22.200 kcal/Nm
 replace the distributor unit 1)(Fig. 1) with the one for LPG
operation supplied with the standard equipment;
 remove the central pipe 2);
 replace the ring nut 3) - 4)(Fig. 1) supplied with the standard
equipment.
2
GB
3
Tab. B
Fig. 1

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rs 190/m3010166

Tabla de contenido