Duct Mounting Overview
1
2
5
Figure 3 Duct Installation Overview
1
Make sure there is a minimum clearance of 5 m (16.5 ft) between the probe body and any
possible humidifier.
2
When installing the transmitter, drill a second hole approximately 30 cm (12 in) from the
installation hole, towards the direction of the air flow, and plug it with a removable seal.
This second hole is intended for later use in reference measurement with another device
when calibrating or adjusting the transmitter.
3
Check that the duct diameter is suitable for the probe body (see
(page
7)). Ideally, the sensor (probe head) should be installed in the middle of the duct.
4
Maximum air flow speed: 50 m/s (with sintered filter).
5
Avoid installing the transmitter in dead legs. Supersaturation can occur in areas where
there is no air flow.
6
Do not install the probe in a downward angle. Condensation can travel to the sensor along
the probe body if the probe points down.
7
Install the probe in a 90° angle so that the sensor is placed as close to the middle of the
duct as possible.
CAUTION!
sensor inside the duct.
8
6
Avoid installing in a location where condensation can fall on the
3
4
7
90°
Transmitter Dimensions
M212049EN-C