Start-Up Genie Complete
Press [OK] to Exit
3.3.3 Multi-pump Multicontrol
This example is for four pumps, constant pressure control.
Starting from the first inverter to the last, configure each inverter with same parameters values.
Multi-pump Control
Multi Master MulCtl
Pump Address
Application Type
Constant Pressure
Pressure Control Units
Ramp Time
Regulation Band
Number of Pumps
Number of standby pumps
Would you like to Autoset
the rest of the settings?
1
bar
Fast
20%
2
0
Yes
8. Programming Completed. Select OK to Exit from
Start-up Genie.
1. Select Multipump operation from the list below.
Refer to the full manual for details.
• Fixed Speed Follower
• Multi Master Synch
• Multi Master MulCtl
2. Select Pump Multi-pump address from 1 to 4.
3. Selectable applications are Constant Pressure,
Flow Control and Level Control. Refer to the full man-
ual for details.
4. Select Pressure Control Unit.
5. Select Ramp Time. Refer to
tion
for details.
6. Set desired pressure regulation band for Double
Ramp Control Logic. Refer to
tion
for details.
7. Select Number of Pumps, from two to four.
8. Select Number of Standby Pumps.
9. Select Yes to Autoset the rest of the settings. Refer
to
Autoset Parameters Extract
en - Original instructions
Ramp Control descrip-
Ramp Control descrip-
for details.