Compatibilidad Electromagnética; Aislamiento - Bticino F4N200 Manual De Instalación

Ocultar thumbs Ver también para F4N200:
Tabla de contenido

Publicidad

Precisión
Precisión en la energía activa:
Precisión en la energía reactiva:
Marcado CE
The F3N300 product complies with:
The requirements of the European directive on electromagnetic compatibility (EMC) no. 89/336/CEE dated 3 May
1989, modified by directive no. 92/31/CEE dated 28 April 1992 and by directive no. 93/68/CEE dated 22 July 1993.
Low voltage directive no. 73/23/CEE dated 19 February 1973, modified by directive no. 93/68/CEE dated 22 July
1993, modified by directive n° 2006/95/CE.
Compatibilidad electromagnética
Immunity to electrostatic discharges:
Immunity to radiated radio-frequency fields:
Immunity to electrical fast transients/bursts:
Immunity to surge immunity:
Immunity to conducted disturbances:
Immunity to power frequency magnetic fields:
Conducted and radiated emissions:
Immunity to voltage dips and short interruptions:
Climat
Operating-temperature range:
Storage temperature range:
Humidity:
Salt mist:
Características mecánicas
Vibration from 10 to 50 Hz:

Aislamiento

Installation category:
Degree of pollution:
Rated impulse withstand voltage:
Front face:
Electric safety:
Caracterìsticas del PMD
Tipo de característica
Función (eventual) de evaluación de la calidad de la
alimentación
Clasificación de los PMD
Temperatura
Humedad + Altitud
Clase de rendimiento de funcionamiento de la potencia activa
o de la energía activa (si la función se encuentra disponible)
IEC 62053-22, Class 0,5S
IEC 62053-23, Class 2
IEC 61000-4-2 - Level III
IEC 61000-4-3 - Level III
IEC 61000-4-4 - Level III
IEC 61000-4-5 - Level III
IEC 61000-4-6 - Level III
IEC 61000-4-8 - Level III
CISPR11 - Class A
IEC 61000-4-11
IEC 60068-2-1/IEC 60068-2-2
-10 °C to +55 °C
IEC 60068-2-1/IEC 60068-2-2
-20 °C to +85 °C
IEC 60068-2-30 - 95 %
IEC 60068-2-52 - 2,5 % NaCl
IEC 60068-2-6 - 2 g
III (480 VAC ph /ph)
2
IEC 60947-1 - V imp: 4 kV
Class II
IEC 61010-1
Conformidad con IEC 61557-12 Edition 1 (08/2007)
Ejemplo de valores
característicos posibles
Standard multifunction meter
Otras características
complementarias
-
SD
K55
-
0,5
-
-
-
-
-
43

Publicidad

Tabla de contenido
loading