Siemens SIGNUM 3SF5 Instructivo página 4

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

C
ommissioning
Fig. 5
Clip
AS-i cable
Fig. 6
Fig. 7
Step 6
M12 position switch
1
2
Fig. 8
4
3
Status-LEDs
AS-i
Fig. 9
FAULT
ADDR.
F- IN 2
green: AS-I
red:
FAULT
F- IN 1
NTERFACE
SIEMENS
SAFETY AT WORK
2FI S0.B
CE
Fig. 10
Technical data
Electrical data as per
AS-i specification
Inputs
Mechanical data
Temperature range
Material
Approval
4
To start up the module, carry out the following steps:
Step
Procedure
1
Set the address if you want to carry out addressing prior to installation.
2
Lay the AS-i cable with the broad side facing downwards (Fig. 5).
3
Fasten the clip to the F adapter in accordance with the code
(the clip code determines the polarity).
4
Fasten the clip and the AS-i cable to the AS-i F adapter (Fig. 6).
5
Set the address if you have not carried out step 1.
6
Caution: Attach strain relief! (Fig. 7)
7
Mounting the Heavy Duty Fixing
If the 3SF5402-1AA01 ASI-F adapter is to be removed and then later remounted, the enclosed half-
shells must also be mounted (Fig.11).
Notes
• Cover the address jack which is not used with the screw plug, in order to comply with the specified
degree of protection.
• Each code table may occur only once in one AS-i line connected to the safety
monitor.
PRESS
For contact assignment for M12 (Fig. 8, category 4)
Pin 1
Channel 2
Terminal for next position switch
Pin 2
Channel 2
Terminal for next position switch
Pin 3
not used
Pin 4
not used
The following table shows the status - LEDs and their operating states:
AS-i / FAULT
green
Communication OK
Off
No voltage present at AS-Interface-Chip
red permanent
Communication failed
red/yellow flashing
Slave has address "0"
Channels
F - IN1
LED on: contact closed
F - IN2
LED on: contact closed
I/O configuration (hex)
ID code (hex)
Total current drain
Reverse polarity protection
Low sigal range
High signal range
Degree of protection
Weight
Dimensions in mm (h x w x d)
Rated temperature
Ambient temperature
Storage temperature
Casing
cUL
Fig.11
1
Operating state (Fig.9)
Operating state (Fig. 10)
0
B
≤ 45 mA
I
yes
contact open
contact closed
≥ 5 mA)
I
dynamic (I
in
peak
IP 65 / IP 20 (emergency stop on front panel)
approx. 30 g
IP 20
65 x 31 x 50 max (with screw plug, 40 ± 5 Ncm)
IP 65
58 x 31 x 50 max (with screw plug, 40 ± 5 Ncm)
T
25 °C
u
T
- 25 °C to 70 °C
a
T
- 40 °C to 85 °C
s
Polycarbonate
NBR for O-ring in the M12 sockets
CLASS II ONLY
max. 0,7 Nm
2
3ZX1012-0SF30-0AN1