8. Configuration via display and operating unit
3. Select "Level" and confirm with [↵].
4. Select "Unit" and confirm with [↵].
5. Select length unit and confirm with [↵].
» Length unit is set.
6. Select "Density" and confirm with [↵].
7. Select "Density unit" and confirm with [↵].
8. Select density unit and confirm with [↵].
» Density unit is set.
9. Select "Density value" and confirm with [↵].
10. Set digit using [▲] [▼] and confirm with [↵].
» The cursor moves to the next digit.
» Repeat for each digit.
» Density value is set.
11. Go back two menu levels using [ESC].
Select "Mode" and confirm with [↵].
12. Select "Level" and confirm with [↵].
» Mode is set.
13. Perform a mounting correction.
→ See chapter 8.8 "Mounting correction (offset)".
» Level measurement is configured.
WIKA operating instructions, model DMSU21A