10 Technical data
CAUTION
Maschinenfabrik Reinhausen GmbH 2021
10.8 Digital outputs
TAPCON® 230 basic
Relay outputs DC 24 up to 220 V, AC
230 V
TAPCON® 230 pro/expert/AVT
Switching voltage
Contact load capacity
Table 21: Digital outputs DO
300
V
100
50
U
40
30
20
10
0.1
Figure 37: Contact load capacity of digital outputs with resistive load
Electric shock!
The outputs of the DO assembly have plug-based electrical isolation. A mix-
ture of voltage ranges (e.g. extra low voltage and low voltage) or various
phases within a plug can lower the protection against electric shock.
► Use the same voltage ranges within a plug.
► Use the same phase within a plug.
7820658/01 EN
▪ 8 relays
▪ 4 groups per module, electrically iso-
lated
▪ 16 relays
▪ 4 groups per module, electrically iso-
lated
24 V DC/48 V DC/60 V DC/110 V DC/22
0 V DC 110 V AC/230 V AC
Min.: 5 V DC, 10 mA
Max. DC: See diagram
Max. AC: 250 V AC; 5 A (resistive load-
ing), 2 A (at cos φ = 0.4)
0.2
0.5
1
2
I
5
10
A
20
®
TAPCON
230
61